About the auxiliary contact adapter, Required tools, Install the auxiliary contact adapter – Rockwell Automation 2100 Install External Auxiliary Contact Adapter User Manual
Page 2
2
Rockwell Automation Publication 2100-IN003C-EN-P - April 2014
CENTERLINE Motor Control Centers Install External Auxiliary Contact Adapter
About the Auxiliary Contact
Adapter
Use these instructions to install an external auxiliary contact adapter in
CENTERLINE 2100 Series Q…Y units with Cutler-Hammer Westinghouse
Circuit Breakers
(1)
(HMCP600, LD, HLD, LDC, MDL, HMDL, ND, HND,
and NDC).
This auxiliary contact kit (2100H-N23) is to be used with the following auxiliary
contacts: catalog numbers 2100H-N19 or 2100H-N20.
Required Tools
You need a socket set with extension and a torque wrench to complete the
installation.
Install the Auxiliary Contact
Adapter
Follow these steps and refer to
Assembly of External Auxiliary Contact Parts
to
install the auxiliary contact adapter.
1. Verify that all power has been disconnected and turn operator handle to
the OFF/O position.
2. Verify the parts list, see
Assembly of External Auxiliary Contact Parts
.
3. Attach the external auxiliary contact assembly to the mounting plate by
using two 1/4-20 thread-rolling screws and torque to 55 lb•in (6.2 N•m).
Assembly of External Auxiliary Contact Parts.
4. Attach the actuator to the circuit breaker bail by using two 1/4-20
thread-rolling screws.
5. Position the actuator so the screws are centered in slots and torque to
55 lb•in (6.2 N•m).
6. Install auxiliary contacts (Catalog Number 2100H-N19 or 2100H-N20).
7. Turn operator handle to ON/I position to be sure that the auxiliary
contacts change state.
8. Check continuity to be sure proper operation of auxiliary contacts.
(1) These circuit breakers are available for Bulletin 2100 Series Y and earlier motor control centers.
ATTENTION: De-energize all power sources to the motor control center before
installing auxiliary contact adapter. Failure to de-energize all power sources can
result in severe injury or death.