Install the Connector Kits

The connection system is comprised of three components:

Input wiring connectors that plug into the leftmost drive and receive input wiring for
mains AC and 24V DC.

AC bus, DC bus, and 24V DC T-connectors that plug into the drives downstream from
the first drive where AC, DC, and/or 24V control power is shared. DC bus
T-connectors also plug into the first drive where DC bus power is shared.

Bus bars that connect between drives to extend the mains AC bus, DC bus, and 24V DC
control power from drive-to-drive.

This example illustrates the mains AC input wiring connector, T-connectors, and bus-bar
connectors. The 24V bus and DC bus systems connect in a similar way.

(1)

Due to the higher amp rating of frame 3 drives, input wiring connectors for frame 3 drives (catalog number 2198-H070-ADP-IN) are slightly larger
than connectors for frame 1 and 2 drives (catalog number 2198-H040-ADP-IN).

(2)

Due to the extra width of frame 3 drives, bus-bar connectors between frame 3 drives are slightly longer (85 mm) than connectors between frame 2
and frame 1 drives (55 mm).

(3)

DC bus T-connectors latch on both sides when inserted into the drive. To remove the DC bus T-connector, at least one latch must be pried away with
a non-conductive probe.

SHOCK HAZARD: To avoid hazard of electrical shock, perform all mounting and wiring of the
Kinetix 5500 drives and shared-bus connector kits prior to applying power. Once power is applied,
connector terminals can have voltage present even when not in use.

IMPORTANT

When the shared-bus connection system is used, the zero-stack tab and cutout must be
engaged between adjacent drives.

2198-H

xxx-xxx Drive System (top view)

Frame 2 drives are shown.

Drive with largest amp rating must be

leftmost drive.

Input Wiring Connector

(1)

AC T-connectors

Bus-bar Connectors

(2)

(AC bus-bars shown)

Input Wiring

(AC input wiring is shown)

Zero-stack Tab

and Cutout Engaged

DC Bus Connector Latch

DC Bus T-connector

(3)