Specifications – Rockwell Automation 1792D-8BT0LP ArmorBlock LP2 8 Sinking Input Module User Manual
Page 9
ArmorBlock LP2 8 Sinking Input Module
9
Publication 1792D-5.47 - August 1999
Specifications
This product has been tested at an Open DeviceNet Vendor Association,
Inc. (ODVA) authorized independent test laboratory and found to comply
with ODVA Conformance Test. Please contact the ODVA website
(http://www.odva.org) for listing of products tested by ODVA independent
test labs for further details.
8 Input Module - Cat. No. 1792D-8BT0LP
Sinking Input Specifications
Max
Min
Inputs per block
8 - 3 wire or dry contact PNP devices
Sensor Source Current (per input)
50mA
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5Vdc
Off-state Current
1.5mA
Indicators
Network Status - red/green
Module Status - red/green
Point LED- yellow
Communication Rate
• 125Kbps @ 500 meters(1600 feet) for thick
cable, flat media length 375 meters (1230 feet)
• 250Kbps @ 200 meters(600 feet) for thick
cable, flat media length 150 meters (492 feet)
• 500Kbps @ 100 meters (330 feet) for thick
cable, flat media length 75 meters (246 feet)
DeviceNet Power Voltage
Current
25V dc
125mA (no sensors)
11V dc
500mA (8 sensors @
50mA per sensor)
Dimensions (assembled to base)
inches - (millimeters)
1.023H x 2.7W x 4.72D
(26)H x (68.5)W x (120)D
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration
-25 to 60
o
C (-13 to 140
o
F)
-25 to 80
o
C (-13 to 176
O
F)
Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6
Conductors
Publication DN-6.7.2
Enclosure
Meets or exceeds IP67
Agency Certification
(when product is marked)
• CE marked for all applicable directives
Product Data (user information)
Publication 1792-2.1