Configure your input module, Set the input filter time, Input filter time – Rockwell Automation 1794-IB8_IB16_IB16K_IB32 Flex I/O Digital Input Modules Installation Instructions User Manual
Page 4
4
Publication 1794-IN093C-EN-P - December 2009
1794-TB32 or -TB32S Terminal Base Wiring for the 1794-IB32
Configure Your Input Module
Configure your input module by setting bits in the configuration word (write word).
Set the Input Filter Time
To set the input filter time, set the associated bits in the output image table
(complementary word) for the module.
For example, to increase the off-to-on filter time to 4 ms for all inputs at address
rack 1, module group 0, (using 1794-IB32 as an example), set bits and program as
shown below.
Refer to the following Input Filter time chart for other bit settings.
Input Filter Time
Specifications - 24V DC 8 Input Module, Cat. No. 1794-IB8
Specifications - 24V DC 16 Input Module, Cat. Nos. 1794-IB16 and
1794-IB16K
Dec.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Oct.
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
Read 1
(1794-IB16,
1794-IB32)
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
I0
Read 1
(1794-IB8)
Not used
I7
I6
I5
I4
I3
I2
I1
I0
Read 2
(1794-IB16)
C = Counter Input value of input 15
Read 2
(1794-IB32)
I31
I30
I29
I28
I27
I26
I25
I24
I23
I22
I21 I20 I19 I18 I17 I16
Write 1
(1794-IB8)
Not used
Input Filter
0…07
Write 1
(1794-IB16)
Not used
CF
CR
Not used
Input Filter
12…15
Input Filter
0…11
Write 1
(1794-IB32)
Not used
Input Filter FT
0…31
Not used
Where I = Input
C = Counter value for input 15
FT = Input filter time
CR = Counter reset
CF = Counter fast - where 1 = fast input (raw data), 0 = standard input filtered data
NOTE: C, CR and CF not available when used with any series 1794-ASB or 1794-ASB2 remote I/O adapter
modules.
+V1 COM1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16
35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
34
NC
+V2 = Terminals 43, 45, 47, and 49
Inputs
+V1 COM1 +V1 COM1 +V1 COM1
+V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
+V1 = Terminals 35, 37, 39, and 41
COM1 = Terminals 36, 38, 40, and 42
NC = No connections (terminals 16, 33, 34, and 51)
COM2 = Terminals 44, 46, 48, and 50
NC
NC
(1794-TB32 shown)
Inputs
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
FT = 0…7 (1794-IB8)
FT = 0…11 (1794-IB16)
1794-IB16
O:010
Dec.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
Oct.
FT = 12…15
FT = 0…31
1794-IB32
1
0
0
7
6
5
4
3
FLL
I:000
00
Fill File
Source
Destination
Length
#O:010
1
Write FT to complement
of input module.
Write filter time on system startup.
7
6
5
4
3
2
1
0
0
1
0
= 4 Octal or 4 Decimal
2
1
0
= 44 Octal or 36 Decimal
0
1
0
1
0
0
1794-IB8
1794-IB16
1
0
0
= 4 Octal or 4 Decimal
1
0
0
1794-IB32
09
08
10
11
12
13
14
15
Bits
Description - Filter Time
Filter Time
02
01
00
Inputs 0…07 (1794-IB8)
1794-IB8, -IB16, -IB16K, -IB32
02
01
00
Inputs 0…11 (1794-IB16, -IB16K)
05
04
03
Inputs 12…15 (1794-IB16, -IB16K)
10
09
08
Inputs 0…31 (1794-IB32)
Off to On/On to Off
0
0
0
Filter time 0 (default)
0.25 ms
0
0
1
Filter time 1
0.5 ms
0
1
0
Filter time 2
1 ms
0
1
1
Filter time 3
2 ms
1
0
0
Filter time 4
4 ms
1
0
1
Filter time 5
8 ms
1
1
0
Filter time 6
16 ms
1
1
1
Filter time 7
32 ms
Specification
Description
Number of inputs
8, nonisolated, sinking
Module location
1794-TB3 or 1794-TB3S terminal base unit
On-state voltage, min.
10V DC
On-state voltage, nom.
24V DC
On-state voltage, max.
31.2V DC
On-state current, min.
2.0 mA
On-state current, nom.
8.0 mA
On-state current, max.
12.0 mA
Off-state voltage, max.
5.0V DC
Off-state current, max.
1.5 mA
Input impedance
4.6K
Ω
Isolation voltage
50V (continuous), Basic Insulation Type, between field side and system
No isolation between individual channels
Type tested at 850V DC for 60 s
Flexbus current
20 mA at 5V DC
Power dissipation
3.5W max. @ 31.2V DC
Thermal dissipation
Max. 11.9 BTU/hr @ 31.2V DC
Specification
Description
Number of inputs
16 (1 group of 16), nonisolated, sinking
Module location
1794-TB3 or 1794-TB3S terminal base unit
Mounting
Refer to the derating curve.
On-state voltage, min.
10V DC
On-state voltage, nom.
24V DC
On-state voltage, max.
31.2V DC
On-state current, min.
2.0 mA
On-state current, nom.
8.0 mA
On-state current, max.
12.0 mA
Off-state voltage, max.
5.0V DC
Off-state current, max.
1.5 mA
Input impedance
4.6K
Ω
Isolation voltage
50V (continuous), Basic Insulation Type, between field side and system
No isolation between individual channels
Type tested at 707V DC for 60 s
Flexbus current
30 mA at 5V DC
Power dissipation
6.1W max. @ 31.2V DC
Thermal dissipation
Max. 20.8 BTU/hr @ 31.2V DC