Configure the user protocol – Rockwell Automation Logix5000 Controllers ASCII Strings Programming Manual User Manual
Page 12
![background image](/manuals/579884/12/background.png)
Chapter 1 Communicating with an ASCII device
To configure the user protocol, use these steps.
1. In the Controller Properties dialog box, click the User Protocol tab.
•
Enter a buffer size greater than or equal to the greatest number of
characters in a transmission. Twice the number of characters is a good
guideline.
•
For ABL or ARL instructions, enter termination characters to mark the
end of the data. For ASCII codes, see
If the device sends
Then
Tips
One termination character
•
In the Termination Character 1 box, type the
hexadecimal ASCII code for the first character.
•
In the Termination Character 2 box, type $FF.
For printable characters, such as 1 or A, type the character.
Two termination characters
In the Termination Character 1 and 2 boxes, type the
hexadecimal ASCII code for each character.
•
For AWA instruction, enter append characters. For ASCII codes, see
To append
Then
Tips
One character
•
In the Append Character 1 box, type the
hexadecimal ASCII code for the first character.
•
In the Append Character 2 box, type $FF.
For printable characters, such as 1 or A, type the character.
Two characters
In the Append Character 1 and 2 boxes, type the
hexadecimal ASCII code for each character.
Configure the User Protocol
12