Rockwell Automation 1734D-IA8XOA8 POINTBlock ac 8 Input/8 Output Module User Manual
Page 10

10 POINTBlock ac 8 Input/8 Output Module
Publication 1734-5.22 - February 2000
Number of POINT I/O
Expansion Modules
12 maximum added at expansion port
Isolation Voltage
1250Vrms or 2121V dc for 1s between user power and
DeviceNet
Indicators
1 red/ green module status indicator
1 red/green network status indicator
16 I/O status indicators (8 input/8 output)
Power Dissipation
2.0W maximum @ 24V dc
Power Consumption
8.2W maximum @ 24V dc
Field Power Bus
Supply Voltage
Voltage Range
Supply Current
24V dc nominal
10-28.8V dc
10A max
Dimensions Inches
(Millimeters)
3.00H x 2.36W x 5.25L
(76.2 Hx 60.0W x 133.4L)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
-20 to +55
o
C (-4 to +131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
14 AWG (2.5mm
2
) - 22 AWG (0.25mm
2
) solid or
stranded max
3/64 inch (1.2mm) insulation max
2
1
Terminal Base Screw
Torque
5-7 pound-inches (0.5-0.6 Nm)
Field Wiring Terminations
DeviceNet
1 - Black Wire
-V
2 - Blue Wire
CAN Low
3 - Bare Wire
Drain
4 - White Wire CAN High
5 - Red Wire
+V
Field Power Supply
0 - No Connection1 - No Connection
2 - No Connection3 - No Connection
4 - AC return
5 - AC return
6 - AC power
7 - AC power
Mass
13.88 oz/393.50 grams