Configuring the KF3

Chapter 3

3Ć6

Table 3.B

Basic Configuration Parameters (continued)

Parameter Number

Parameter

Description

Factory Default

RSĆ232C Parameters

RSĆ232C Baud Rate

Baud rate of the RSĆ232C link between the host computer and the KF3.

The host computer and KF3 must be set to the same baud rate.
Possible rates are 300 (03), 600 (06), 1200 (12), 2400 (24), 4800 (48),

9600 (96), 19200 (19).

9600 baud (96).

RSĆ232C Parity

Parity of the characters on the RSĆ232C link. Parity can be None (00) or

Even (01). The host computer and KF3 must have the parity set to the

same value.

None (00).

DF1 Device Category

Sets the communication protocol to be used on the RSĆ232C link.

Choices are DF1 fullĆduplex (00), DF1 halfĆduplex slave, local mode (01),

or DF1 halfĆduplex slave, remote mode (02). See Chapter 4,

Communicating with the KF3, for details.

FullĆduplex (00).

Error Detection

Two forms of error detection are available on the DF1 link: BCC Block

Check Code (00) or CRC16 Cyclic Redundancy Check (01).
The application program running on the host computer must use the same

error detection as the KF3. Refer to your application user's manual for

information on the type of error detection it is using, and set the KF3 to the

same value.

BCC (00).

Flow Control

Determines whether modem handshake lines are used for flow control:

disabled (00) or enabled (01).
Flow control is normally enabled when communicating with a modem.

Disabled (00).

Duplicate Message

Detection

Determines whether duplicate message detection is disabled (00) or

enabled (01).
When duplicate message detection is enabled, the KF3 will acknowledge

(and discard) duplicate messages.

Enabled (01).

Other Parameters

Submenu Parameters

Lets you into the submenu to set the advanced communication

parameters; the data display will show two dashes.
See the section on Advanced Communication Parameters for more

information.

N/A

Series and Revision

Displays the series and revision level of the module. The first digit shows

the series (AĆJ), the second the revision (AĆJ). For example, Series A,

Revision B is displayed as AB." You cannot set this value.

N/A