5a (also see – Rockwell Automation 1762-OW16 Relay Output Module User Manual
Page 16
16 MicroLogix 1762-OW16 Relay Output Module
Publication 1762-IN009C-EN-P - July 2013
Isolated groups
Group 1: Outputs 0…7
Group 2: Outputs 8…15
Output group to backplane isolation
Verified by one of the following dielectric tests: 1836V AC for 1 sec.
or 2596V DC for 1 sec.
265V AC working voltage (IEC Class 2 reinforced insulation)
Output group to output group isolation
Verified by one of the following dielectric tests: 1836V AC for 1 sec.
or 2596V DC for 1 sec.
265V AC working voltage (basic insulation)
150V AC working voltage (IEC Class 2 reinforced insulation)
Vendor ID code
1
Product type code
7
Product code
121
Relay Contact Ratings
Volts (max.)
Continuous
Amps per Point
(max.)
Amperes
(1)
(1)
Surge Suppression – Connecting surge suppressors across your external inductive load will extend the life of the relay
contacts. For additional details, refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication
Voltamperes
Make
Break
Make
Break
240V AC
2.5A
7.5A
0.75A
1800 VA
180 VA
120V AC
15A
1.5A
125V DC
1.0A
0.22A
(2)
(2)
For DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied DC voltage. For example, 28 VA/48V DC = 0.58A. For DC voltage applications less than 14V, the make/break rating
for relay contacts cannot exceed 2A.
28 VA
24V DC
2.0A
1.2A
28 VA
Output Specifications
Attribute
Value