Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…55 °C (-4…131 °F)

Temperature, surrounding
air, max.

55 °C (131 °F)

Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6, (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80%AM from 80 MHz…2000 MHz

10V/m with 200 Hz 50% pulse 100%AM @ 900 MHz

10V/m with 200 Hz 50% pulse 100%AM @ 1890 MHz

1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4kV @ 2.5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM @ 150 kHz…80 MHz