beautypg.com

Install the armorpoint ac output module – Rockwell Automation 1738-OA2M12AC3 ArmorPoint AC Output Module, Series A User Manual

Page 5

background image

Publication 1738-IN007A-EN-E - June 2004

ArmorPoint AC Output Module, Series A 5

3. Mount the base using #8 (M4) screws.

4. Ground the system using the ground lug connection. (The

ground lug connection is also a mounting hole.)

Install the ArmorPoint AC
Output Module

To install the ArmorPoint AC output module, proceed as follows.

1. Using a bladed screwdriver, rotate the keyswitch on the

mounting base clockwise until the number 8 aligns with the
notch in the base.

2. Position the module vertically above the mounting base. The

module will bridge two bases.

Ground lug connection

Latching mechanism

Keyswitch-

Set to position 8 for
the 1738 AC output
module

Mounting base

43675

1738-OA2M12AC3/A

12V ac

0.75Amp

Out

0

1

0

1

M

N

O

D

E
T

Module will bridge two bases.

43778