beautypg.com

Rockwell Automation 1771-IN ac (24V) Input Module Installation Instructions User Manual

Page 6

background image

Publication 1771-IN082A-EN-P - February 2005

6 AC (24V) Input Module

1. Make certain all power is removed from the module before making

wiring connections.

2. Swing the wiring arm up into position on the front of the module. The

locking tab on the module will secure it into place.

3. Connect one terminal of your 2-wire input device to terminals 0 thru 7.

Use stranded 14 or 16 AWG (2.0-1.5mm

2

) to minimize the voltage drop

over long cable distances.

ATTENTION

Remove power from the 1771 I/O chassis backplane and
field wiring arm before removing or installing the I/O
module.

• Failure to remove power from the backplane or wiring

arm could cause module damage, degradation of
performance, or injury.

• Failure to remove power from the backplane could

cause injury or equipment damage due to possible
unexpected operation.

IMPORTANT

The field wiring arm terminal identification number is not
the same as the number of the bit which controls that
output

A

O

1

2

3

4

5

6

7

B

L2

L2

AC Low

L1

24V AC High

Not used

Input 0

Input 1

Input 2

Input 3

Input 4

Input 5

Input 6

Input 7

(Actual wiring runs in this direction.)

1

1902-I