Input specifications – Rockwell Automation 1769-IQ16F Compact 24V dc Sink/Source Input Module User Manual
Page 14
14 Compact 16-point 24V dc Sink/Source High-speed Input Module
Publication 1769-IN064A-EN-P - April 2003
Input Specifications
Specification
1769-IQ16F
Voltage Category
24V dc (sink/source
(1)
)
(1)
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the field device.
Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field power supply are sinking field devices. Field
devices connected to the positive side (+V) of the field supply are sourcing field devices. Europe: DC sinking input and
sourcing output module circuits are the commonly used options.
Operating Voltage Range
10 to 30V dc at 30°C (86°F)
10 to 26.4V dc at 60°C (140°F)
Number of Inputs
16
Bus Current Draw (max.)
110 mA at 5V dc (0.55W)
Heat Dissipation
3.55 Total Watts (The Watts per point, plus the minimum Watts, with
all points energized.)
Digital Filter
OFF to ON 0s, 100
µs, 500µs, 1ms, 2ms
ON to OFF 0s, 100
µs, 500µs, 1ms, 2ms
Hardware Delay
OFF to ON 100
µs (typical)
300
µs (maximum)
ON to OFF 250
µs (typical)
1ms (maximum)
Off-State Voltage (max.)
5V dc
Off-State Current (max.)
1.5 mA
On-State Voltage (min.)
10V dc
On-State Current (min.)
2.0 mA
Inrush Current (max.)
250 mA
Nominal Impedance
3K
Ω
IEC Input Compatibility
Type 1+
Power Supply Distance Rating
8 (The module may not be more than 8 modules away from the power
supply or controller.)
Input Point to Bus (Compact Bus)
Isolation
Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.
75V dc working voltage (IEC Class 2 reinforced insulation)
Isolated Groups
Group 1: inputs 0 to 7
Group 2: inputs 8 to 15
Isolated groups operate in either sink or source configurations.
Input Group to Input Group Isolation
Verified by one of the following dielectric tests: 1200V ac for 1 sec. or
1697V dc for 1 sec.
75V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code
1
Product Type Code
7
Product Code
69