Rockwell Automation 1793-OB16 Flex Integra Output Module Install Inst User Manual
Page 8
Publication 1793-5.9 - December 1999
PN 957259-16
Supersedes publication 1793-5.9 - September 1999
© (1999) Rockwell International Corporation.Printed in USA
8
FLEX Integra 16 Protected Source Output Module
Delay Time
Off to On
On to Off
0.5ms maximum
1.0ms maximum
Flexbus Current
80mA maximum
Power Dissipation
5W @ 31.2V dc
Thermal Dissipation
17 BTU/hr @ 31.2V dc
Indicators
16 yellow channel status indicators
Fusing
Outputs are electronically protected
External dc Power Voltage
Current
19.2-31.2V dc (5% ac ripple)
60mA
Dimensions
Inches
(Millimeters)
2.72H x 3.7D x 2.17W
(69H x 94D x 80W)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Nonoperating
Vibration
0 to +55
o
C (32 to +131
o
F)
-40 to +85
o
C (-40 to +185
o
F)
5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+1)ms pulse width
Tested to 50g peak acceleration, 11(+1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6
Conductors
Wire Size
Category
12 gauge (4mm
2
) to 18 gauge (0.75mm
2
) stranded
wire rated @ 75
o
C minimum
3/64 in (1.2mm) maximum insulation
2
1
Screw Terminal Torque
5-7 lb-in (0.5-0.6Nm)
Agency Certification
(when product is marked)
• C-UL listed
• C-UL Class I, Division 2 Groups A, B, C and D
certified
• UL listed
• CE marked for all applicable directives
• C-Tick marked for all applicable acts
1
Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”
Specifications - 16 Protected Output Module Cat. No. 1793-OB16P and -OB16PS