Compact I/O Analog Output Module
Publication 1769-IN087A-EN-P - August 2009
Wire Size and Terminal Screw Torque
Each terminal accepts two wires with the following restrictions.
Configure the 1769-OF4 Module
The following I/O memory mapping lets you configure the 1769-OF4 module.
Output Data File
For each module, slot x, words 0…3 in the output data file contain the control
program’s directed state of the module’s analog output channels. Word 4 contains
the cancel output-channel-clamp alarm control bits.
The bits are defined as follows:
•
SGN = Sign bit in 2’s complement format.
•
NU = Not used. Bit must be set to 0.
•
CHOx = Cancel High Clamp Alarm Latch for Output x: Allows each output
high-clamp-alarm latch to be individually cancelled. NOTE: Cancel = 1.
•
CLOx = Cancel Low Clamp Alarm Latch for Output x: Allows each output
low-clamp-alarm-latch to be individually cancelled. NOTE: Cancel = 1.
Wire Type
Wire Size
Terminal Screw
Torque
Retaining Screw
Torque
Solid
Cu-90 °C (194 °F)
14…22 AWG
(2.08…0.33 mm
2
)
0.68 N•m (6 lb•in)
0.46 N•m (4.1 lb•in)
Stranded
Cu-90 °C (194 °F)
16…22 AWG
(1.31…0.33 mm
2
)
0.68 N•m (6 lb•in)
0.46 N•m (4.1 lb•in)
Word/Bit 15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word 0
SGN
Analog Output Data Channel 0
Word 1
SGN
Analog Output Data Channel 1
Word 2
SGN
Analog Output Data Channel 2
Word 3
SGN
Analog Output Data Channel 3
Word 4
NU
NU NU NU NU NU NU NU CL
O3
CH
O3
CL
O2
CH
O2
CL
O1
CH
O1
CL
O0
CH
O0