Specifications
General Specifications
Specification
Value
Dimensions
118 mm (height) x 87 mm (depth) x 35 mm (width)
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width)
height including mounting tabs is 5.43 in.
Approximate Shipping Weight
(with carton)
280g (0.61 lbs.)
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Operating Temperature
0°C to +60°C (32°F to +140°F)
Operating Humidity
5% to 95% non-condensing
Operating Altitude
2000 meters (6561 feet)
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 inches maximum peak-
to-peak
Relay Operation: 2G
Shock
Operating: 30G panel mounted (20G DIN rail mounted)
Relay Operation: 7.5G panel mounted (5G DIN rail
mounted)
Non-Operating: 40G panel mounted (30G DIN rail
mounted)
Agency Certification
• C-UL certified (under CSA C22.2 No. 142)
• UL 508 listed
• CE compliant for all applicable directives
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions
EN50081-2 Class A
Electrical /EMC:
The module has passed testing at the following levels:
• ESD Immunity (IEC1000-4-2)
• 4kV contact, 8 kV air, 4 kV indirect
• Radiated Immunity (IEC1000-4-3)
• 10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
• Fast Transient Burst (IEC1000-4-4) • 2 kV, 5 kHz
• Surge Immunity (IEC1000-4-5)
• 2 kV common mode, 1 kV differential mode
• Conducted Immunity (IEC1000-4-6) • 10V, 0.15 to 80 MHz
1
1. Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range
is 30 MHz to 1000 MHz.