© (1999) Rockwell International Corporation.Printed in USA
Output Signal Delay Time
Off to On
On to Off
0.5ms maximum
1.0ms maximum
Flexbus Current
80mA maximum
Power Dissipation
4.2W @ 31.2V dc
Thermal Dissipation
14.3 BTU/hr @ 31.2V dc
Indicators
16 yellow channel status indicators
Fusing
Outputs are electronically protected
External dc Power Voltage
Current
19.2-31.2V dc (5% ac ripple)
49mA
Dimensions
Inches
(Millimeters)
2.72H x 3.7D x 3.2W
(69H x 94D x 80W)
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Nonoperating
Vibration
0 to +55
o
C (32 to +131
o
F)
-40 to +85
o
C (-40 to +185
o
F)
5 to 95% noncondensing
Tested to 30g peak acceleration, 11(+1)ms pulse width
Tested to 50g peak acceleration, 11(+1)ms pulse width
Tested 5g @ 10-500Hz per IEC68-2-6
Conductors
Wire Size
Category
12 gauge to 18 gauge (4mm
2
to 0.75mm
2
)
stranded wire rated @ 75
o
C minimum
3/64 in (1.2mm) maximum insulation
2
1
Screw Terminal Torque
5-7 lb-in (0.5-0.6Nm)
Agency Certification
(when product is marked)
• C-UL Listed
• C-UL Class I, Division 2 Groups A, B, C and D certified
• UL listed
• CE marked for all applicable directives
• C-Tick marked for all applicable acts
1
Use this category information for planning conductor routing as described in publication 1770-4.1, “Wiring and
Grounding Guidelines for Noise Immunity.”
Specifications - 16 Protected Output Module Cat. No. 1793-OV16P and -OV16PS