Specifications – Rockwell Automation 1792D-2BVA2D ArmorBlock MaXum 2 Input with Alarm/2 Output Module Series B User Manual
Page 12
12 ArmorBlock MaXum 2 Input with Alarm/ 2 Output Module Series B
Publication 1792D-IN015B-EN-P - September 2000
Specifications
2 Input with Alarm / 2 Output Module - Cat. No. 1792D-2BVA2D
Input Specification
Max.
Min.
Inputs per block
2 - 3 wire or dry contact PNP or NPN devices or 2 - 4
wire PNP or NPN devices
Sensor Source Current (per input)
100mA
-
Off-Wire Sense Current
0.5mA
-
On-state Voltage
25V dc
10V dc
On-state Current
10mA
2mA
Off-state Voltage
5V dc
-
Off-state Current
-
1.5mA
Output Specification
Max.
Min.
Outputs per block
2 sourcing outputs labeled 00 and 01
Output Auxiliary Voltage
30V
10V
On-state Voltage Drop
1V
-
On-state Current
1A
-
Off-state Leakage
1.5mA
-
Module Current (all outputs)
2A
-
Surge Current - for 10ms,
repeatable every 2s
2.4A
-
No Load Sense Current (On-state)
0.18A
-
General Specifications
Indicators
Net/Mod Status - red/green
Logic Status - red/green
Auxiliary Power - green
Point LED - yellow/orange/red
Communication Rate
•125Kbps @ 500 meters(1600 feet) for thick cable,
flat media length 375 meters
•250Kbps @ 200 meters(600 feet) for thick cable,
flat media length 150 meters
•500Kbps @ 100 meters (330 feet) for thick cable,
flat media length 75 meters
DeviceNet Power Voltage
Current
Refer to the graphs in the
Overview section of the
ArmorBlock I/O Family Technical
Data, pub. no.
1792-TD001B-EN-P.
25V dc max
150mA max (no sensors)
11V dc min up to .8A
(2 sensors @100mA
per sensor)
Auxiliary Power
Voltage
Current
30V dc max
2A max
10V dc min
2A max