background image

Programming

Chapter 3

3Ć12

3.

Enter a data address and a result address.

If we select a data address of 201 and a result address of 305, the AF4
establishes the data table format shown in Figure 3.3. Be careful not to select
data and result addresses so close together that the addresses of the operands
following the data address overlap your result address. The data address
eventually contains three digits of operand 1. The AF4 reserves the next three
higher addresses for digits 4 through 6 of operand 1 and digits 1 through 6 of
operand 2. The result address contains the most significant three digits of the
result and the next higher address contains the least significant three digits.

Figure 3.3

AF4 Addition Function Formal After Address Entry

17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0

S

Digit 1

(MSD)

Digit 2

Digit 3

Bit No.

Data Address

Digit 5

Digit 6

Digit 4

(LSD)

Operand 1

S

Digit 1

(MSD)

Digit 2

Digit 3

Digit 5

Digit 6

Digit 4

(LSD)

Operand 2

S

Digit 1

(MSD)

Digit 2

Digit 3

Result Address

Digit 5

Digit 6

Digit 4

(LSD)

Result

D ER

E

E = Enable Bit (1 = Function in Progress)

S = Sign Bit (1= Negative)

D = Done Bit (1 = Function Complete)

ER = Error Bit (1 = Overflow)

MSD = Most Significant Digit

LSD = Least Significant Digit

11482

201

202

203

204

305

306