Environmental specifications, General specifications – Rockwell Automation 1734-OB2_OB4_OB8, Series C POINT I/O Output Module Installation Instructions User Manual
Page 19
POINT I/O Output Module 19
Publication 1734-IN018C-EN-E - April 2013
Isolation voltage
50V (continuous), Reinforced Insulation Type
Type tested @ 2500V DC for 60 s, field-side to system
External DC power supply voltage, nom
24V DC
External DC power voltage range
10...28.8V DC
External DC power supply current
1734-OB2 – 8 mA
1734-OB4 – 16 mA
1734-OB8 – 32 mA
Dimensions, HxWxD, approx.
56.0 x 12.0 x 75.5 mm
(2.21 x 0.47 x 2.97 in.)
Wiring category
(1)
2 – on signal ports
Wire size
Determined by installed terminal block
Weight, approx.
1734-OB2 – 32.60 g (1.15 oz)
1734-OB4 – 33.17 g (1.17 oz)
1734-OB8 – 35.4 g (1.25 oz)
North American Temp Code
1734-OB2 – T4A
1734-OB4 – T4A
1734-OB8 – T4
IEC Temp Code
T4
(1)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publicatio
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40...85 °C (-40...185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
General Specifications
Attribute
Value