Rockwell Automation 1793-OB4E FLEX INTEGRA 4 PROTECTED OUTPUT User Manual
Page 7
FLEX Integra 4 Protected Output Module
7
Publication 1793-5.2 - January 2000
WARNING:
Explosion Hazard
• Substitution of components may impair
suitability for Class I, Division 2.
• Do not replace components unless power
has been switched off or the area is known
to be non-hazardous.
• Do not disconnect equipment unless power
has been switched off or the area is known
to be non-hazardous.
• Do not disconnect connectors unless
power has been switched off or the area is
known to be non-hazardous. Secure any
user-supplied connectors that mate to
external circuits on this equipment by using
screws, sliding latches, threaded
connectors, or other means such that any
connection can withstand a 15 Newton (3.4
lb.) separating force applied for a minimum
of one minute.
• Batteries must only be changed in an area
known to be non-hazardous.
AVERTISSEMENT : Risque d’explosion
• La substitution de composants peut rendre
ce matériel inadapté à une utilisation en
environnement de
Classe I, Division 2.
• Couper le courant ou s'assurer que
l’environnement est classé non dangereux
avant de remplacer des composants.
• Couper le courant ou s’assurer que
l’environnement est classé non dangereux
avant de débrancher l'équipement.
• Couper le courant ou s'assurer que
l’environnement est classé non dangereux
avant de débrancher les connecteurs. Fixer
tous les connecteurs fournis par l'utilisateur
pour se brancher aux circuits externes de cet
appareil à l 'aide de vis, loquets coulissants,
connecteurs filetés ou autres, de sorte que
les connexions résistent à une force de
séparation de 15 Newtons (1,5 kg - 3,4 lb.)
appliquée pendant au moins une minute.
• S'assurer que l'environnement est classé
non dangereux avant de changer les piles.
CUL logo is a registered trademark of the
Underwriters Laboratories.
Le sigle CUL est une marque déposée de la
Underwriters Laboratories.
Specifications - 4 Protected Output Module Cat. No. 1793-OB4P and -OB4PS
Module Type
4 digital output - sourcing, protected
1793-OB4P - screw-cage terminations
1793-OB4PS - spring-clamp terminations
Module Location
DIN rail mounting
Number of Channels
1 group of 4, nonisolated
On-state Voltage
10-31.2V dc; 24V dc nominal
On-state Current
1-500mA per channel
Off-state Voltage
31.2V dc maximum
Off-state Current
0.5mA maximum leakage
Channel Impedance
1.0
Ω (0.5V dc maximum drop)
Surge Current
1.5A for 50ms, repeatable every 2s
Isolation Voltage
Channel to system - 850V dc for 1s
Channel to channel - None
Delay Time
Off to On
On to Off
0.5ms maximum
1.0ms maximum
Flexbus Current
20mA maximum
Power Dissipation
1.3W @ 31.2V dc
CUL Hazardous Location Approval
Approbation d’utilisation dans des
environnements dangereux par la CUL