beautypg.com

Rockwell Automation 1734-FPD, Series B POINT I/O Field Potential Distributor Modules Installation Instructions User Manual

Page 13

background image

POINT I/O Field Potential Distributor Modules 13

Publication 1734-IN059D-EN-E - April 2013

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...55 °C (-4...131 °F)

Temperature, surrounding air, max 55 °C (131 °F)

Temperature, nonoperating

IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)

IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)

IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10...500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV @ 2.5 kHz on power ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports

Conducted RF immunity

IEC61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz