Rockwell Automation 1785-L11B_L20B_L30B_L40B_L40L_L60B_L60L_L80B INSTL INSTR ENHANCED PLC-5 PC User Manual
Installation instructions
Publication1785Ć5.13 April 1996
Enhanced PLCĆ5
Programmable Controller
Firmware Upgrade
(Catalog Numbers 1785-L11B, -L20B, -L30B,
-L40B, -L40L, -L60B, -L60L, -L80B)
These instructions describe:
•
an important safety precaution involving static electricity
discharges
•
how to upgrade the processor firmware
For more information about PLC-5 processors, see the Enhanced and
Ethernet PLC-5 User Manual, publication number 1786-6.5.12. For
more information, contact your Allen-Bradley service representative.
Printed circuit board components and Programmable Read-only
Memory (PROM) devices can be damaged during routine handling
and installation. Follow these precautions to reduce static electricity
discharges before you upgrade the processor firmware.
•
Handle the printed circuit boards and PROMs by the case or
carrier without touching the pins or the edge connector.
•
Use a static-free workstation.
•
Connect the static-free workstation to ground through a minimum
200K ohm resistance.
•
Wear a grounded, conductive wrist strap with a minimum 200K
ohm resistance.
•
Ground all tools before you begin to upgrade the firmware.
•
Control the relative humidity of the installation area – ideal
conditions are 40% to 60% relative humidity.
AĆB
Installation Instructions
Using These Instructions
Before You Install ...