MicroLogix™ 1762-IQ8 DC Input Module
1762-IN004A-US-P
Input Specifications
Specification
1762-IQ8
Voltage Category
24V dc (sink/source)
(1)
(1)
Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the
field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are
driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of
the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the
field supply are sourcing field devices.
Operating Voltage Range
10 to 30V dc at 30°C (86°F)
10 to 26.4V dc at 55°C (131°F)
Number of Inputs
8
Bus Current Draw (max.)
50 mA at 5V dc (0.25W)
Heat Dissipation (max.)
3.7 Total Watts
Signal Delay (max.)
On Delay: 8.0 ms
Off Delay: 8.0 ms
Off-State Voltage (max.)
5V dc
Off-State Current (max.)
1.5 mA
On-State Voltage (min.)
10V dc
On-State Current
2.0 mA min. at 10V dc
8.0 mA nominal at 24V dc
12.0 mA max. at 30V dc
Inrush Current (max.)
250 mA
Nominal Impedance
3K
Ω
IEC Input Compatibility
Type 1+
Power Supply Distance Rating
6
Isolated Groups
Group 1: inputs 0 to 7 (internally connected commons)
Input Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1200V ac for 1
sec. or 1697V dc for 1 sec.
75V dc working voltage (IEC Class 2 reinforced insulation)
Vendor I.D. Code
1
Product Type Code
7
Product Code
96