FLEX I/O 240V AC Digital Input and Output Modules 3

Publication 1794-IN123B-EN-P - May 2009

Connecting Wiring for your 1794-OM16 Module

(using a 1794-TBN or TBNF Terminal Base)

1. Connect individual output wiring to terminals 0...15 on the 16-33 row (B),

and the 34-51 row (C) as indicated in Table 1.

2. Auxiliary terminal blocks are required to connect the associated L2

common for each channel. Connect the L2 side of the load together and
then connect to L2 on the power supply.

3. Connect 240V AC power L1 to terminal 34 on the 34-51 row (C).
4. Connect 240V AC common L2 to terminal 16 on the 16-33 row (B).
5. If daisychaining power to the next terminal base, connect a jumper from

terminal 51 (240V AC L1) on this base unit to terminal 34 on the next base
unit.

6. If continuing 240V AC common (L2) to the next base unit, connect a

jumper from terminal 33 (240V AC common L2) on this base unit to
terminal 16 on the next base unit.

Note: Total current draw through terminal base connection is limited to 10A.
Separate power connections to each terminal base may be necessary.

Configure Your AC Module

Set the Input Filter Time for the 1794-IM16 Module

You can increase the input filter time (FT) for channels 00...15 by setting the
corresponding bits in the output image table (complementary word) for the module.

For example, setting bits 00, 01 and 02 as shown below sets the off-to-on filter time
for inputs 00...11 to 12 ms. For other settings, refer to the Input Filter Time table.

To increase the filter time, set the bits according to Input Filter Times.

Input Filter Times

Specifications

Image Table Memory Map for the 1794-IM16 Module

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

Input Data

Read

Bit 15 Counter

Write

R

EF

EC

Reserved

Filter Time 12...15

Filter Time 0...11

Where

I = Input status

R = Reserved

EF = Enable Filter 0 = Enabled
EC = Enable Counter 0 = Enabled

Image Table Memory Map for the 1794-OM16 Module

Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

Not used - Set to 0

Write

O15

O14

O13

O12

O11

O10

O9

O8

O7

O6

O5

O4

O3

O2

O1

O0

Where

O = Output

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

FT = 12...15

FT = 0...11

O:010

Dec.

1

0

0

7

6

5

4

3

FLL

I:000

00

Fill File
Source

Destination

Length

#O:010

1

Write FT to
complement of
input module

Write filter time on system startup.

2

1

0

= 44 Octal or 36 Decimal

0

1

0

1

0

0

Bits

Description

Maximum Filter

Time (ms)

02

01

00

Filter Time for inputs 00...11

Selected Filter
Time

05

04

03

Filter Time for inputs 12...15

Off to On

On to Off

0

0

0

Filter Time 0 (Default)

256

μ

s

7.5

26.5

0

0

1

Filter Time 1

512

μ

s

8

27

0

1

0

Filter Time 2

1 ms

9

28

0

1

1

Filter Time 3

2 ms

10

29

1

0

0

Filter Time 4

4 ms

12

31

1

0

1

Filter Time 5

8 ms

16

35

1

1

0

Filter Time 6

16 ms

24.5

44

1

1

1

Filter Time 7

32 ms

42

60.5

Specifications - FLEX I/O 240V AC Input Module 1794-IM16

Attribute

Value

Number of I/O channels

16, nonisolated

Module location

Cat. No. 1794-TBN

On-state voltage

159V AC min @ 47...63 Hz

240V AC nom @ 47...63 Hz

264V AC max @ 47...63 Hz

On-state current

5.30mA minimum @ 159V AC, 47Hz

11mA nominal @ 240V AC, 60Hz

13.29mA maximum @ 264V AC, 63Hz

Off-state voltage, max

40V AC

Off-state current, max

2.6 mA

Isolation voltage

250V (continuous), Basic Insulation Type

Type tested at 1706V DC for 60 s, between field side and system

No isolation between individual channels

+5V Field Bus current

32 mA

Power dissipation, max

6 W @ 264V AC

Thermal dissipation, max

20.47 BTU/hr @ 264V AC

Indicators (field side)

16 yellow status indicators

Input impedance

22.2 k

Ω

Input filter time

(1)

Off to On

On to Off

(1)

Input off-to-on filter time is the time from a valid input signal to recognition by the module.

Input on-to-off filter time is time from the input signal dropping below the valid level to recognition by the module.

Refer to Input Filter Times table

Inrush current, max

450mA