beautypg.com

Mounting dimensions, Specifications – Rockwell Automation 1786-RPCD ControlNet Modular Repeater Dual Copper Module User Manual

Page 20

background image

20 ControlNet Dual Copper Repeater Module

Publication 1786-IN001B-EN-P - May 2004

Mounting Dimensions

The figure below shows the dimensions for mounting the module.

Specifications

Specification

Value

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0 to 60

°

C (32 to 140

°

F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

-40 to 85

°

C (-40 to 185

°

F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5 to 95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5g@10 - 500Hz

Operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30g

Non-operating Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50g

4.44in

(111mm)

3.6in

(90mm)

4.048in

(101.2mm)

2.76in

(69mm)

4.0in

(100mm)

31495-M