Rockwell Automation 1734D-IA8XOW8S POINTBlock ac 8 Input/8 Relay Output Module User Manual
Page 11

POINTBlock ac 8 Input/8 Relay Output Module 11
Publication 1734-5.23 - February 2000
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
-20 to +55
o
C (-4 to +131
o
F)
-40 to 85
o
C (-40 to 185
o
F)
5 to 95% noncondensing
30g peak acceleration, 11(±1)ms pulse width
50g peak acceleration, 11(±1)ms pulse width
Tested 5g @ 10-500Hz per IEC 68-2-6
Conductors Wire Size
Category
14 AWG (2.5mm
2
) - 22 AWG (0.25mm
2
) solid or
stranded max
3/64 inch (1.2mm) insulation max
2
1
Terminal Base Screw Torque
5-7 pound-inches (0.5-0.6 Nm)
Field Wiring Terminations
DeviceNet
1 - Black Wire
-V
2 - Blue Wire
CAN Low
3 - Bare Wire
Drain
4 - White Wire CAN High
5 - Red Wire
+V
Field Power Supply
0 - No Connection1 - No Connection
2 - No Connection3 - No Connection
4 - AC return
5 - AC return
6 - AC power
7 - AC power
Mass
13.87 oz/393.41 grams
Agency Certification (when
product is marked)
• C-UL Listed
• C-UL Class I, Division 2 Groups A, B, C and D
certified
• UL listed
• CE marked for all applicable directives
• C-Tick marked for all applicable acts
1
Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1,