Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60 °C (32…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11:

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz

10V/M with 200 Hz 50% Pulse 100%AM @ 900 MHz

10V/M with 200 Hz 50% Pulse 100%AM @ 1890 MHz

1V/M with 1 kHz sine-wave 80%AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on ControlNet ports

Surge transient immunity

IEC 61000-4-5:

±2 kV line-earth (CM) on ControlNet ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz