Environmental specifications – Rockwell Automation 1756-CN2_CN2R, Series B ControlLogix ControlNet Interface Module User Manual
Page 33
Environmental Specifications
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)
Temperature, storage
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal
Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Emissions
CISPR 11:
Group 1, Class A
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/M with 200 Hz 50% Pulse 100%AM @ 900 MHz
10V/M with 200 Hz 50% Pulse 100%AM @ 1890 MHz
1V/M with 1 kHz sine-wave 80%AM from 2000...2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on ControlNet ports
Surge transient immunity
IEC 61000-4-5:
±2 kV line-earth (CM) on ControlNet ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
ControlLogix ControlNet Interface Module 33
Publication
1756-IN607A-EN-P - February 2008