General Specifications - 1794-IG16, 1794-OG16
Specification
Description
Terminal base screw torque
Determined by installed terminal base
Dimensions (with module installed)
H x W x D
94 x 94 x 69 mm
3.7 x 3.7 x 2.7 inches
External dc power supply voltage
5V dc nominal
External dc power voltage range
4.5...5.5V dc
(includes 50mV p-p ripple)
External dc power supply current
1794-IG16 - 210mA max @ 5V dc
1794-OG16 - 100mA @ 5V dc
North American temp code
T4A
Keyswitch position
1
Enclosure type rating
None (open-style)
Wire type
Shielded (Power and I/O)
Wire size
Determined by installed terminal base
Wiring category
(1)
3- on signal ports
2- on power ports
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
.
Environmental Specifications
Specification
Description
Operating temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0...55 °C (32…131 °F)
Storage temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC60068-2-6 (Test Fc, Operating):
5g @ 10...500Hz
Shock
IEC60068-2-27 (Test Ea, Unpackaged shock):
Operating 30g
Non-operating 50g
Emissions
CISPR 11:
Group 1, Class A (with appropriate enclosure)
ESD immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
1V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2k V at 5kHz on power ports
±2k V at 5kHz on signal ports
Surge transient immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on power ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certifications
(when product is marked)
(1)
(1)
See the Product Certification link at
details.
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E194810.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)