8 ArmorPoint I/O Field Potential Distributor, Series A

Specifications

Following are specifications for the 1738 ArmorPoint FPD.

1738-FPD Field Potential Distributor
Inputs Voltage Rating

12V dc, 24V dc nominal

10-28.8V dc range

120V ac, 240V ac nominal

Input Current

10A maximum

Operating Voltage

12/24V dc, 120/240V ac

Backplane Output Current

Pass Through

Keyswitch Position

8

General Specifications
Indicators

None

PointBus Current

Pass Through

Power Consumption

None

Power Dissipation

None

Thermal Dissipation

None

Isolation Voltage

(continuous-voltage withstand rating)

50V rms, 120V rms/240V rms

Tested at 1528V ac rms for 60s

Field Power Bus

Supply Voltage


Supply Current


264V ac maximum,

12V dc, 24V dc, 10-28.8V dc range

120V ac, 240V ac, 50/60 Hz

10A maximum

Dimensions

Inches (Metric)

1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 to 60°C (-4 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g

Non-operating 50g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

ESD Immunity

IEC 61000-4-2:

6kV contact discharges

8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity

IEC 61000-4-4:

±4kV at 5kHz on power ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports