Configure Your Input Module
You configure your input module by setting bits in the configuration word (word 3).
Set the Input Filter Time for the 1794-IH16
To set the input filter time, set the associated bits in the output image
(complementary word) for the module.
Input Filter Times
Dec
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Oct
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
Read
I15
I14
I13
I12
I11
I10
I9
I8
I7
I6
I5
I4
I3
I2
I1
I0
Write
Not used = Set to 0
Input filter
FT1 12-15
Input filter
FT0 0-11
Where I = Input
FT0 = Input filter time for inputs 0-11
FT1 = Input filter time for inputs 12-15
Bits
Description
Selected Filter Time
02
01
00
Filter Time for inputs 00...11
05
04
03
Filter Time for inputs 12...15
0
0
0
Filter Time 0 (Default)
0.25ms
0
0
1
Filter Time 1
0.50ms
0
1
0
Filter Time 2
1ms
0
1
1
Filter Time 3
2ms
1
0
0
Filter Time 4
4ms
1
0
1
Filter Time 5
8ms
1
1
0
Filter Time 6
16ms
1
1
1
Filter Time 7
32ms
O:010
FT = 00...11
09 08 07 06 05 04 03 02 01 00
15 14 13 12 11 10
Dec.
FT = 12...15
Specifications - FLEX I/O 125V dc Digital Input Module
Specification
Description
Number of I/O channels
16, nonisolated, sinking
Module location
Cat. No. 1794-TB3, -TB3S
On-state voltage
90V dc minimum
125V dc nominal
146V dc maximum
On-state current
1.0mA minimum
2.0mA nominal at 125V dc
3.0mA maximum
Off-state voltage
20V dc maximum
Off-state current
0.8mA minimum
Input impedance
60K ohms nominal
Isolation voltage
250V (continuous), Basic Insulation Type, between field side and system
Type tested at 1706V dc for 60 s, between field side and system
No isolation between individual channels
Flexbus current
80mA
Power dissipation
6W maximum @ 146V dc
Thermal dissipation
20.472 BTU/hr @ 146V dc
Indicators (field side indication,
customer device driven)
16 yellow status indicators
Input filter time
(1)
Off to On
On to Off
(1)
Input off-to-on filter time is the time from a valid input signal to recognition by the module.
Input on-to-off filter time is time from the input signal dropping below the valid level to recognition by the module.
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
0.25ms, 0.5ms, 1ms, 2ms, 4ms, 8ms, 16ms, 32ms
General Specifications
Specification
Description
Terminal base screw torque
Determined by installed terminal base
Dimensions (with module installed)
H x W x D
94 x 94 x 69 mm
3.7 x 3.7 x 2.7 inches
External dc power supply voltage
125V dc nominal
External dc power voltage range
90...146V dc (includes 5% ac ripple)
North American temp code
T4
Keyswitch position
1
Enclosure type rating
None (open-style)
Wire size
Determined by installed terminal base
Wiring category
(1)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
1770-4.1
.
2- on signal ports