beautypg.com

Specifications, General specifications – Rockwell Automation 1762-IA8 MICROLOGIX 120 VAC INPUT MODULE User Manual

Page 11

background image

MicroLogix™ 1762-IA8 120V ac Input Module

11

1762-IN002A-US-P

Specifications

General Specifications

Specification

Value

Dimensions

90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.543 in. (height) x 3.425 in. (depth) x 1.575 in. (width)
height including mounting tabs is 4.33 in.

Approximate Shipping Weight
(with carton)

209 g (0.46 lbs.)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +55°C (-32°F to +131°F)

Operating Humidity

5% to 95% non-condensing

Operating Altitude

2000 meters (6561 feet)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak

Shock

Operating: 30G panel mounted

Agency Certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous Environment Class

Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)

Noise Immunity

NEMA standard ICS 2-230

Radiated and Conducted Emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity (IEC1000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier

Fast Transient Burst (IEC1000-4-4)

2 kV, 5 kHz

Surge Immunity (IEC1000-4-5)

2 kV common mode, 1 kV differential mode

Conducted Immunity (IEC1000-4-6)

10V, 0.15 to 80 MHz

(1)

(1)

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency
range is 30 MHz to 1000 MHz.