Output specifications – Rockwell Automation 1769-IF4XOF2 Compact Combination Analog Module User Manual
Page 21
Compact™ Combination Analog I/O Module 21
Publication 1769-IN057A-EN-P - July 2001
Output Specifications
Maximum Overload at Input
Terminals
(6)
Voltage Terminal: 20V continuous, 0.1 mA
Current Terminal: 32 mA continuous, +5V dc
Input Group to Bus Isolation
500V ac or 710V dc for 1 minute (qualification test)
30V ac/30V dc working voltage (IEC Class 2 reinforced insulation)
Channel Diagnostics
Over-range by bit reporting
(1)
The over-range flag will come on when the normal operating range is exceeded. The module will continue to convert the
analog input up to the maximum full scale range. The flag automatically resets when within the normal operating range.
(2)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input
signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above
ground).
(3)
For proper operation, both the plus and minus input terminals must be within 0 to +10V dc of analog common.
(4)
Includes offset, gain, non-linearity and repeatability error terms.
(5)
Repeatability is the ability of the input module to register the same reading in successive measurements for the same input
signal.
(6)
Damage may occur to the input circuit if this value is exceeded.
Output Specification
1769-IF4XOF2
Number of Outputs
2 single-ended
Analog Normal Operating Ranges
(1)
Voltage: 0 to 10V dc
Current: 0 to 20 mA
Full Scale Analog Ranges
Voltage:0 to 10.5V dc
Current: 0 to 21 mA
Converter Type
Resistor String
Resolution (max.)
8 bits plus sign (Sign is always positive, Bit 15 = 0.)
Response Speed per Channel
0.3 ms for rated resistance and rated inductance
3.0 ms for rated capacitance
Current Load on Voltage Output
10 mA max.
Resistive Load on Current Output
0 to 300
Ω
(includes wire resistance)
Load Range on Voltage Output
> 1 k
Ω
at 10V dc
Max. Inductive Load
(Current Outputs)
0.1 mH
Max. Capacitive Load
(Voltage Outputs)
1 µF
Overall Accuracy at 25°C
(2)
Voltage Terminal: ±0.5% full scale
Current Terminal: ±0.5% full scale
Overall Accuracy at 0 to 60°C
Voltage Terminal: ±0.6% full scale
Current Terminal: ±1.0% full scale
Accuracy Drift with Temperature
Voltage Terminal: ±0.01% full scale per °C
Current Terminal: ±0.01% full scale per °C
Input Specification
1769-IF4XOF2