Troubleshooting – Rockwell Automation 1771-P7 AC(120/220V) 16A Installation Instructions User Manual

Page 8

background image

P/S

Active

12627ĆI

AC (120/220V) 16A Power Supply

8

Publication 1771Ć5.39 Ċ December 1995

3. Connect the ac power line to the terminal strip on the

power supply.

!

ATTENTION: You must connect a 14 AWG wire
from the GND terminal to the ground bus to provide
an adequate safety ground.

Line 1

Line 2 or

neutral

Ground

Bus

ac power connectors

Grounding electrode

conductor

ac power

(customer

supplied)

A 3A 250V normalĆblow fuse protects the input line L1 from drawing more than 3 amperes.

14 AWG

L1

L2/N

GND

central ground bus (earth ground)

low side of the line power

high side of the line power

Connect

12626ĆI

The power supply has a green P/S ACTIVE LED that provides status
indication during power supply operation.

Normal operation

If indicator is Then

on

off

it may be due to:

input voltage not within specified range

blown fuse

overcurrent

Important: If a shutdown condition occurs, wait 15 seconds before

attempting to apply power.

For additional assistance, contact your local Allen-Bradley
representative.

Troubleshooting