Rockwell Automation 1771-OWNA Contact Output Module Installation Instructions User Manual
Page 14
Contact Output Module
14
Publication 1771-IN038B-EN-P - August 2002
Surge Transient Immunity
IEC61000-4-5
+1kV line-line (DM) and +2kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type Rating
None (open-style)
Keying
Between 6 and 8
Between 16 and 18
Field Wiring Arm
1771ĆWN
Wiring Arm Screw Torque
9 pound-inches (1.0Nm)
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for Class I,
Division 2 Group A, B, C, D Hazardous Locations
CE
4
European Union 89/336/EECEMCDirective,
compliant with:
EN 61000-6-4, Industrial Emissions
EN 50082-2, Industrial Immunity
EN 61326, Meas./Control/Lab., Industrial Requirements
EN 61000-6-2, Industrial Immunity
European Union 73/23/EECLVD Directive,
compliant with:
EN 61131-2, Programmable Controllers
C-Tick
4
Australian Radiocommunications Act, compliant with:
AS/NZS 2064, Industrial Emissions
1
Spikes, peaks and surges must be within the power rating. Resistive loads only. ac and dc power = 30W max.
2
Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure that surges do not exceed either the
voltage or current rating of the module.
3
You use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Industrial
Automation Wiring and Grounding Guidelines.
4
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates and other certification details