14 SynchLink 4-port Splitter Block
Publication 1751-IN002A-EN-P - March 2001
Specifications
Communication Rate
5M bit/s
Splitter Block Power Consumption
5V dc input from 1751-SLBA
0.300 A @ 5.1V dc
Environmental Conditions
(1)
(1)
This product must be mounted within a suitable system enclosure to prevent personal injury resulting from accessibility to
live parts. The interior of this enclosure must be accessible only by the use of a tool. This industrial control equipment is
intended to operate in a Pollution Degree 2 environment, in overvoltage category II applications, (as defined in IEC
publication 664A) at altitudes up to 2000 meters without derating.
Operating Temperature
0ºC - 60ºC
Storage Temperature
-40ºC - 85ºC
Relative Humidity
5 to 95%, 0ºC - 60ºC non-condensing
Shock
Operating
30g peak acceleration, 11 (
±
1)ms pulse width
Non-operating
50g peak acceleration, 11 (
±
1)ms pulse width
Vibration
Tested 5 g @ 10 - 500Hz per IEC 68-2-6
Fiber Optic Cable
Fiber Type
200/230 micron HCS (Hard Clad Silica)
Fiber Termination Type
Versalink V-System
Assemblies
Cable assemblies can be ordered from Allen-Bradley, catalog
number 1403-CFxxx (xxx = length in meters); or from Lucent
Technologies, Specialty Fiber Technologies division.
Maximum Length
300 meters
Minimum Length
1 meter
Agency Certifications
When product is marked:
Listed Industrial Control Equipment
Certified Process Control Equipment
Certified Class I, Division 2, Group A, B, C, D
Marked for all applicable directives
marked for all applicable acts
N223