Environment and Enclosure
About the Assembly
Prepare the wires
The total wire size range for the RTBs is 22…14 AWG. The wire may be stranded or solid.
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic
compatibility in residential and other environments due to
conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed
for those specific environmental conditions that will be
present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic.
The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may
contain additional information regarding specific enclosure type ratings that are required to comply with certain product
safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements,
Allen-Bradley publication
1770-4.1.
• NEMA Standards 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided
by different types of enclosure.
ATTENTION
Do not use wire ferrules on wires connected to the terminals on the modules.
Wire Size Range,
AWG
Number
of Wires
Strip Length
8-position RTB
12-position RTB
22…14 AWG
1
16
±1 mm (0.63±0.03 in)
14
±1 mm (0.55±0.03 in)
2
18
±1 mm (0.71±0.03 in)
16
±1 mm (0.63±0.03 in)
Mounting Base
Removable
Terminal Block
(RTB)
RTB Removal
Handle
Mechanical Keying
(orange)
Interlocking Side
Pieces
DIN Rail Locking
Screw (orange)
44895
1734-TB3 shown
Strip Length
1
5
5
9
4
-
N
P
9
0
0
2
e
n
u
J
-
P
-
N
E
-
B
3
1
0
N
I
-
4
3
7
1
n
o
i
t
a
c
il
b
u
P
Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
Additional Resources
You can view or download publications at
http://www.literature.rockwellautomation.com
. To order
paper copies of technical documentation, contact your local Rockwell Automation distributor or sales
representative.
Signal terminal current, max
1734-RTBS and 1734-RTB3S: 2A
Isolation voltage
250V, Basic Insulation Type, field-side to system
Type tested at 1000V AC for 60 s
(1)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Groundi
ng
Guidelines, publication
1770-4.1 .
Environmental
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Certifications (1734-TB3 and 1734-TB3S only)
Certification (when product
is marked)
(1)
Value
c-UR-us
UL Recognized Component Industrial Control Equipment, certified for US and Canada.
See UL File E195367.
:
h
t
i
w
t
n
a
il
p
m
o
c
,
e
v
i
t
c
e
r
i
D
C
M
E
C
E
/
8
0
1
/
4
0
0
2
n
o
i
n
U
n
a
e
p
o
r
u
E
E
C
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick
Australian Radiocommunications Act, compliant with: AS/NZS CISPR11; Industrial
Emissions
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.
General
Attribute
Value