Rockwell Automation 1794-TB3GK, -TB3GS, -TB3T, -TB3TS, -TBN, -TBNK, -TBNF Flex I/O Terminal Base Units User Manual
Page 5

FLEX I/O Terminal Base Units 5
Publication 1794-IN092E-EN-P - November 2009
Working Voltage and Isolation Voltage Ratings
General
Attribute
Value
Terminal screw
torque
0.56...0.79 Nm (5...7 lb-in) (1794-TB3TK, -TB3G, -TB3GK, -TB2, -TB32, -TB3,
-TB3K, -TB3T)
0.3...0.6 Nm (2.6...5.3 lb-in) (1794-TBKD)
1.4 Nm (12 lb-in) (1794-TBN, -TBNF, -TBNFK, -TBNK)
Supply voltage
range (max)
FLEXBUS: 5V DC, 640 mA
I/O Terminals: 2A max
V/COM Terminals: 125V DC/AC, 50/60Hz, 10A (1794-TB3SK, -TB3TK,-TB2, -TB3,
-TB3K, -TB3S, -TB3TK, -TB3TS)
V/COM Terminals: 31.2V DC/AC, 50/60Hz, 10A (1794-TB3GSK, -TB3G, -TB3GS,
-TB3GK, -TB32, -TB32S
V/COM Terminals: 250V DC/AC, 50/60Hz, 10A (1794-TBN, -TBNF, -TBNFK,
-TBNK)
1794-TBKD only
FLEXBUS: 5V DC, 640 mA
Terminal Block: 120V AC, 50/60Hz, 10A
Disconnecting Switch: 3A, 20m
Ω
ATTENTION
A disconnecting switch does not shut off the current. Make or break a circuit
only under no-load conditions.
Isolation voltage
Capable of 250V (continuous) maximum, Basic Insulation Type, Field Wiring
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TBN, -TBNF,
-TBNFK, -TBNK)
Capable of 125V (continuous) maximum, Basic Insulation Type, Field Wiring
Terminals to FLEXBUS, or the lesser of the installed module (1794-TB3SK,
-TB3TK, -TB3TK, -TB3TSK, -TB2, -TB3, -TB3K, -TB3S, -TB3TS)
Capable of 50V (continuous) maximum, Basic Insulation Type, Field Wiring
Terminals to FLEXBUS, or the lesser of the installed module. (1794-TB3G,
-TB3GS, -TB3GK, -TB3GSK, -TB32, -TB32S)
2500V DC/sec, Field Wiring Terminals to FLEXBUS.
220V DC/sec, Field Wiring Terminals to Functional Ground. (1794-TBKD)
Voltage rating
See Working Voltage and Isolation Voltage Ratings for nominal values
Enclosure type
rating
None (open-style)
Terminal Base 1794-
24V
120V
230V
Isolation Voltage
TBN, TBNK, TBNF, TBNFK
AC/DC
AC/DC
AC/DC
Dependent upon installed
module - refer to individual
installation instructions for
your specific module.
TB2, TB3, TB3K, TB3S, TB3SK
AC/DC
AC/DC
TB3T, TB3TS, TB3TK, TB3TSK
AC/DC
AC/DC
TB3G, TB3GK, TB3GS, TB3GSK
AC/DC
TB32, TB32S
AC/DC
TBKD
DC
AC
General
Attribute
Value
Wire size
0.34... 3.3 mm² (22…12 AWG) solid or stranded copper wire rated at 75 °C (167 °F
) or greater, 1.2 mm (3/64 in.) insulation max. Strip Length: 5-6 mm (0.20...0.24 in.)
(1794-TB3SK, -TB3GSK, -TB3TSK, -TB3GK, -TB3GS, -TB32S, -TB3, -TB3K, -TB3S,
-TB3TS, -TBN, -TBNF, -TBNFK, -TBNK)
0.34…2.1 mm² (22...14 AWG) solid or stranded copper wire rated at 75 °C (167 °F
) or greater, 1.2 mm (3/64 in.) insulation max (1794-TBKD)
0.21... 1.3 mm² (24…16 AWG) stranded copper wire rated at 75 °C (167 °F ) or
greater, 1.2 mm (3/64 in.) insulation max (1794-TB3TK, -TB3G, -TB2, -TB32)
Wiring
category
(1)
Established by installed module
North American
temp code
T4A (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK,
-TB3S,-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S)
T6 (1794-TB2)
IEC temp code
T4 (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S,
-TB3SK, -TB3TS, -TB3TSK, -TBN, -TBNK)
T6 (1794-TB2)
Dimensions,
approx.
94 x 94 x 69 mm (HxWxD) (3.7 x 3.7 x 2.7 in.)
(with module installed in terminal base)
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication
Environmental
Attribute
Value
Operating
temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…70 °C (-4…158 °F) (1794-TB3G, -TB3GS, -TB3GSK, -TB3GK,
-TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3SK, -TB3TS, -TB3TSK,
TB32, -TB32S, -TBN, -TBNK)
0…55 °C (32…131 °F) (1794-TBKD)
-20…55 °C (-4…131 °F) (1794-TBNF, -TBNFK, -TB2)
Non-operating
temperature
IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40…85 °C (-40…185 °F)
-20…85 °C (-4…185 °F) (1794-TBKD)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g (Except for 1794-TBKD)
Non-operating
shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g (Except for 1794-TBKD)
Certifications (when product is marked)
(1)
Attribute Value
UL
(1794-TB2)
UL Listed Industrial Control Equipment. See UL File E65584.
c-UL-us
(1794-TB3G, -TB3GS, -TB3GSK, -TB3GK, -TB3, -TB3K, -TB3T, -TB3TK, -TB3S, -TB3TS,
-TB3SK, -TB3TSK, -TBN, -TBNK, -TB32, -TB32S)
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S.
and Canada. See UL File E194810.
(1794 -TBKD, -TBNF, -TBNFK )
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File
E65584.
CSA
(1794-TB2, -TB3, -TB3K, -TB3T, -TB3S, -TB3TS, -TB3TK, -TB3SK, -TB3TSK, -TBN,
-TBNK, -TB3G, -TB3GK, -TB3GS, -TB3GSK)
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D
Hazardous Locations. See CSA File LR69960C.
(1794-TBNF, -TBNFK)
CSA Certified Process Control Equipment. See CSA File LR54689C.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
General