beautypg.com

Environmental specifications, General specifications – Rockwell Automation 1732E-XXXX ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect User Manual

Page 21

background image

1732E ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect 21

Publication 1732E-IN010C-EN-E - June 2013

Enclosure type rating

Meets IP65/66/67/69K (when marked), and Type 4X Indoor Use Only,
with receptacle dust caps or cable termination

Wiring category

(1)

1 - on signal ports

1 - on power ports

1 - on communications port

Onboard memory type

Ferroelectric Nonvolatile RAM (FRAM)

Onboard memory, capacity, max

6 Kbytes

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

Environmental Specifications

Attribute

Value

Temperature,
operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20…60 °C (-4…140 °F)

Temperature,
ambient, max.

60 °C (140 °F)

Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):

-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10... 500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

CISPR 11

Group 1, Class A

ESD immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

General Specifications

Attribute

Value