Certifications, Environmental specifications – Rockwell Automation 1732D-XXXX PointBlock 16 dc Input Module Installation Instructions User Manual
Page 20

20 DeviceNet 1732 ArmorBlock 16-Point I/O, Series A
Publication 1732D-IN002B-EN-E - January 2013
EFT/B immunity
IEC 61000-4-4:
±3 kV at 5 kHz on power ports
±3 kV at 5 kHz on signal ports
±3 kV at 5 kHz on communications ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±2 kV line-earth(CM) on communications ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MH
Certifications
Certification (when
product is marked)
(1)
Value
c-UL-us
UL Listed Industrial Control Equipment, certified for US and Canada. See UL
File E322657.
CE
European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-Tick
Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
ODVA
ODVA conformance tested to DeviceNet specifications.
(1)
for Declaration of Conformity, Certificates, and other
certification details.
Environmental Specifications
Attribute
Value