Chapter 4, Applying power, Ch 4 - applying power – Rockwell Automation 1608P ProDySC Installation Instructions, 200 A User Manual
Page 15: Chapter
![background image](/manuals/578885/15/background.png)
Rockwell Automation Publication 1608P-IN003A-EN-P - September 2013
15
Chapter
4
Applying Power
•
Before applying power to the ProDySC, make certain there are no metal
filings or any conductive debris in or on any components inside the
ProDySC.
•
Verify ProDySC voltage rating matches ac source voltage.
•
Ensure that all input/output wiring including grounding has been
completed, all covers are replaced, and that access doors are closed and
locked.
•
Place the ProDySC internal circuit breaker in the OFF position.
•
Apply power from the upstream branch protection device. Power will not
flow through to the load. The ProDySC touchscreen will become active.
•
Place the ProDySC internal circuit breaker in the ON position.
•
Ensure that the touchscreen displays "OK" in the upper left corner and
that the nominal voltage, current, and frequency in the status display are
correct.
•
If a "Critical" or "Fatal" system event appears on the touch screen call for
technical support.
•
Verify that the output (load) voltage is present and within its nominal
rating.
NOTICE: Cycling ProDySC input power in the sequence OFF--ON--OFF--ON within a one minute
period will cause a “Limit Cycle Timeout” alarm. In such case sag correction will be inhibited for
one minute, after which the alarm will automatically reset.
WARNING:
The ProDySC is interlocked. Opening ProDySC doors while the
system is in operation will trip the internal circuit breaker and result in loss of
power to protected loads.
ATTENTION:
For Information regarding the operation of ProDySC, including
information on the display screen and maintenance, see Publication 1608P-
UM003A-EN-P