Rockwell Automation 1492-CM800-LD002 Field Wire Conv. Module for Modicon B804-116 to 1756-OA16 or B824-016 User Manual
Page 3

(3)
10000021853
(Version 00)
IV. Conversion Module Wiring Diagram (Continued)
1756-OB16E
1492-CABLE003X
1492-CM800-LD002
Conversion: B824-016 to 1756-OB16E with 1492-CM800-LD002
B824-016 Swing Arm
10
1
9
2
1
3
2
4
3
5
4
6
5
7
6
8
7
9
8
10
11
11
12
12
13
13
14
15
15
16
16
17
17
18
18
20
19
19
20
14
24 VDC
Output 13
Output 15
Output 14
Output 16
Common Grp 2
Output 5
Output 7
Output 6
Output 8
Output 1
Output 3
Output 2
Output 4
Output 9
Output 11
Output 10
Output 12
24 VDC
Common Grp 1
10
DC-0+
OUT-0
1
OUT-1
2
OUT-2
3
OUT-3
4
OUT-4
5
OUT-5
6
OUT-6
7
OUT-7
8
OUT-8
11
OUT-9
12
OUT-10
13
OUT-11
14
OUT-12
15
OUT-13
16
OUT-14
17
OUT-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
DC-1+
20
9
RTN OUT-0
19
RTN OUT-1
+
-
LOAD
Conversion Module Installation and Application Considerations
The B824-016 module output current limits versus 1756-OB16E limits are as follows:
B824-016
1756-OB16E w/ 1492-CABLE003X
a) Current/Point
2A
1A
b) Current/Group
6A
2A
c) Current/Module
12A
4A
d) Surge Current/Pt
5A for 10ms
2A for 10ms
The B824-016 provided a single mechanical fuse per group. The 1756-OB16E is electronically fused per group. Refer to the
1756-OB16E Installation Manual for electronic fusing details.
The 1492-CABLE003X current is limited to 2A per pin.
Refer to your B824-016 and 1756-OB16E Installation Manual wiring schematics and diagrams for more details.
Ensure 1756
output module ratings are not exceeded.
[Reference Doc: 41170-757 (Version 03)]
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.
WARNING