background image

(3)

10000021853

(Version 00)

IV. Conversion Module Wiring Diagram (Continued)

1756-OB16E

1492-CABLE003X

1492-CM800-LD002

Conversion: B824-016 to 1756-OB16E with 1492-CM800-LD002

B824-016 Swing Arm

10

1

9

2

1

3

2

4

3

5

4

6

5

7

6

8

7

9

8

10

11

11

12

12

13

13

14
15

15

16

16

17

17

18

18

20

19

19

20

14

24 VDC

Output 13

Output 15

Output 14

Output 16

Common Grp 2

Output 5

Output 7

Output 6

Output 8

Output 1

Output 3

Output 2

Output 4

Output 9

Output 11

Output 10

Output 12

24 VDC

Common Grp 1

10

DC-0+

OUT-0

1

OUT-1

2

OUT-2

3

OUT-3

4

OUT-4

5

OUT-5

6

OUT-6

7

OUT-7

8

OUT-8

11

OUT-9

12

OUT-10

13

OUT-11

14

OUT-12

15

OUT-13

16

OUT-14

17

OUT-15

18

Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green

DC-1+

20

9

RTN OUT-0

19

RTN OUT-1

+

-

LOAD

Conversion Module Installation and Application Considerations

The B824-016 module output current limits versus 1756-OB16E limits are as follows:

B824-016

1756-OB16E w/ 1492-CABLE003X

a) Current/Point

2A

1A

b) Current/Group

6A

2A

c) Current/Module

12A

4A

d) Surge Current/Pt

5A for 10ms

2A for 10ms

The B824-016 provided a single mechanical fuse per group. The 1756-OB16E is electronically fused per group. Refer to the

1756-OB16E Installation Manual for electronic fusing details.

The 1492-CABLE003X current is limited to 2A per pin.

Refer to your B824-016 and 1756-OB16E Installation Manual wiring schematics and diagrams for more details.

Ensure 1756

output module ratings are not exceeded.

[Reference Doc: 41170-757 (Version 03)]

There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.

WARNING