beautypg.com

Dc-input – Rockwell Automation 1606-XLS240E, -XLS240EA, -XLS240EC, -XLS240E-D Power Supply Reference Manual User Manual

Page 5

background image

All parameters are specified at 24V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM044A-EN-P — March 2014

5

Bulletin 1606 Switched Mode Power Supplies

4. DC-Input

1606-XLS240E, 1606-XLS240EA, 1606-XLS240EC:

DC input

nom.

DC 110-150V

-20%/+25%

DC input range

min.

88-187Vdc

continuous operation

DC input current

typ.

2.37A

110Vdc, at 24V, 10A

1606-XLS240E-D:

DC input

nom.

DC 110-300V

-20%/+25%

DC input range

min.

88-375Vdc

continuous operation

DC input current

typ.

2.37/ 0.85A

110/300Vdc, at 24V, 10A

All units:

Allowed Voltage L/N to Earth

max.

375Vdc

continuous, IEC 62103

Turn-on voltage

typ.

80Vdc

steady state value

Shut-down voltage

typ.

55Vdc

steady state value


Fig. 4-1 Wiring for DC Input

Instructions for DC use:

+

-

Load

L

PE

+

-

Power Supply

AC

Battery

N

DC

a) Use a battery or similar DC source.

For other sources, contact Rockwell Automation.

b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to a earth wire or to the machine

ground.

d) A supply from the intermediate DC-bus of a frequency

converter is not recommended and can cause a
malfunction or damage the unit.