FLEX I/O SCANport
t
Module Installation Instructions
1–5
1203-5.7-- April 1996
Connection Status Word Definition
Connection Status Channel 2 Connection Status Channel 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit:
Not Used V2
ID2
Not Used
V1
ID1
Description
V1
SCANport channel 1 valid data bit. When high (1), the Logic Status
and Analog Feedback values are valid and can be used. When low
(0), the values should not be used.
ID1
SCANport channel 1 connected peripheral port ID number. This three
bit field contains the port number that channel 1 is connected to on the
SCANport device. It should contain a value between 1 and 7. If this
field is 7, then the channel is not connected to the SCANport device, or
the SCANport device may not be powered.
V2
SCANport channel 2 valid data bit. When high (1), the Logic Status
and Analog Feedback values are valid and can be used. When low
(0), the values should not be used.
ID2
SCANport channel 2 connected peripheral port ID number. This three
bit field contains the port number that channel 2 is connected to on the
SCANport device. It should contain a value between 1 and 7. If this
field is 7, then the channel is not connected to the SCANport device, or
the SCANport device may not be powered.
Logic Status/Analog Feedback Definition
The Logic Status and Analog Feedback values are defined within
the product manuals of the connected SCANport device(s).