Bulletin 1494F Disconnect Switch and Accessories for Bulletin 502, 502L, 506, 506X, 512, 512M, 512V,
522E, 522F, 522G, 1232, 1232X, 1232V and 1494G
Handle and Operating Mechanism Installation
1
ATTENTION: Do not install, configure, operate or maintain this product until you have read the product documentation and the documents in the Additional Resources section for installing, configuring, operating or maintaining
equipment. To get the product documentation go to http://www.rockwellautomation.com/literature or contact your local sales office or Rockwell Automation representative.
ATTENTION: Ne pas installer, configurer, exploiter ou maintenir ce produit tant que vous n’avez pas lu sa documentation et les documents de la rubrique Documents connexes pour l’installation, la configuration, l’exploitation et la
maintenance de l’équipement. Pour obtenir de la documentation, rendez-vous sur le site http://www.rockwellautomation.com/literature ou contactez votre agence commerciale Rockwell Automation locale ou son représentant.
ACHTUNG: Für die Installation, Konfiguration, den Betrieb und die Wartung dieses Produkt lesen Sie sich bitte zunächst die Produktdokumentation sowie die Dokumente im Abschnitt „Weitere Informationen“ durch. Die
entsprechende Produktdokumentation finden Sie unter http://www.rockwellautomation.com/literature oder kontaktieren Sie Ihr lokales Vertriebsbüro bzw. einen Rockwell Automation-Mitarbeiter.
ATENCIÓN:
No instale, configure, opere ni mantenga este producto hasta que haya leído la documentación del producto y los documentos en la sección Recursos adicionales para la instalación, configuración, operación o
mantenimiento de equipo. Para conseguir la documentación, diríjase a http://www.rockwellautomation.com/literature o póngase en contacto con su oficina regional de ventas o representante de Rockwell Automation.
ATENÇÃO: Não instale, configure, opere ou mantenha este produto até que você leia a documentação do produto e os documentos na seção Recursos adicionais para a instalação, configuração, operação ou manutenção do
equipamento. Para conseguir a documentação, visite http://www.rockwellautomation.com/literature ou entre em contato con seu escritório de vendas regional ou representante da Rockwell Automation.
ATTENZIONE:
Non installare, configurare, attivare o riparare questo prodotto senza avere prima letto la relativa documentazione nonchè i documenti indicati nella sezione Ulteriori Risore riguardanti l’installazione, la configurazione,
l’attivazione o la riparazione dell’apparecchiatura. Per la documentazione sul prodotto visitare il sito http://www.rockwellautomation.com/literature o contattare l’ufficio vendite o il rappresentate Rockwell Automation di zona.
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or
damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
1
3
4
2
Phase Barrier and Fuse Clip Installation
Lug, Fuse Cover, and Terminal Guard Installation
4
3
7 - 11 lb-in
Disconnect and Trailer Fuse Block Installation
2
40 - 60 lb-in
23 - 37 lb-in
200A
90 - 130 lb-in
400A
30A / 60A / 100A
1
1
1
2
2
3
1
3
2
3
4
2
1
2
60 - 80 lb-in
23 - 37 lb-in
Size 5
Sizes 0 - 4
Switch Mechanism to
Handle Torque
Mounting Torque
NOTES:
1) Handle and
disconnect switch
must both be either
in the “ON” or “OFF”
position for proper
installation.
2) See trailer block
installation table on
back page for correct
fuse spacing.
Lug to Terminal Torque
45 lb-in
60A
150 lb-in
100A
275 lb-in
200A
20 lb-in
30A
275 lb-in
400A
Fuse Clip Torque
16 - 22 lb-in
22 - 37 lb-in
22 - 37 lb-in
40 - 50 lb-in
100A / 200A
400A
40 - 60 lb-in
N/A
60A
90 -110 lb-in
100A
175 - 200 lb-in
200A / 400A
30A
Fuse Clip Torque
22 - 37 lb-in
30A / 60A
Important: Apply grease
to O-Ring seal to retain
into handle groove.
375 lb-in
400A
Power Wire into
Lug Torque