beautypg.com

User configurable items, Storage, Installing/replacing the battery module – Rockwell Automation 1609-U500x Uninterruptible Power Supply User Manual

Page 4: Troubleshooting

background image

User Configurable Items

UPS Settings

Settings are adjusted through PowerChute

software.

Storage

Store the UPS covered in a cool, dry location with the batteries fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.

Installing/Replacing the Battery Module

This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You

may leave the UPS and connected equipment on during the replacement procedure.

Troubleshooting

Access the troubleshooting guide for this UPS through PowerChute software.

Function

Factory Default

User Selectable Choices

Description

Automatic

Self-Test

Every 14 days (336

hours)

• Every 7 days

(168 hours)

• On start up only
• No self-test

Set the interval at which the UPS will execute a self-test.

UPS ID

UPS_IDEN

Up to eight characters

(alphanumeric)

Uniquely identify the UPS (i.e. server name or location) for

network management purposes.

Date of Last Battery
Replacement

Manufacture Date

mm/dd/yy

Reset this date when you replace the battery module.

Minimum Capacity Before
Return from Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 60%
• 75%
• 90%

Specify the percentage to which batteries will be charged
following a low battery shutdown before powering connected

equipment.

Voltage Sensitivity

High sensitivity

High sensitivity
Medium sensitivity
Low sensitivity

The UPS detects and reacts to line voltage distortions by
transferring to battery operation to protect the connected

equipment.
In situations of poor power quality, the UPS may frequently
transfer to battery operation. If the connected equipment can
operate normally under such conditions, reduce the

sensitivity setting to conserve battery capacity and service
life.

Alarm Delay Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms permanently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS receives a

shutdown command and actual shutdown.

Allen-Bradley Company, LLC
Industrial Components Business
1201 South Second Street
Milwaukee, WI 53204-2496 USA
Phone 440.646.5800
www.ab.com

41063-214-01 (1)

This manual is related to the following products: