User configurable items, Storage, Installing/replacing the battery module – Rockwell Automation 1609-U500x Uninterruptible Power Supply User Manual
Page 4: Troubleshooting
User Configurable Items
UPS Settings
Settings are adjusted through PowerChute
software.
Storage
Store the UPS covered in a cool, dry location with the batteries fully charged.
At 5° to 86° F (–15° to 30° C), charge the UPS battery every six months.
At 86° to 113° F (30° to 45° C), charge the UPS battery every three months.
Installing/Replacing the Battery Module
This UPS has an easy-to-replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You
may leave the UPS and connected equipment on during the replacement procedure.
Troubleshooting
Access the troubleshooting guide for this UPS through PowerChute software.
Function
Factory Default
User Selectable Choices
Description
Automatic
Self-Test
Every 14 days (336
hours)
• Every 7 days
(168 hours)
• On start up only
• No self-test
Set the interval at which the UPS will execute a self-test.
UPS ID
UPS_IDEN
Up to eight characters
(alphanumeric)
Uniquely identify the UPS (i.e. server name or location) for
network management purposes.
Date of Last Battery
Replacement
Manufacture Date
mm/dd/yy
Reset this date when you replace the battery module.
Minimum Capacity Before
Return from Shutdown
0 percent
• 0%
• 15%
• 30%
• 45%
• 60%
• 75%
• 90%
Specify the percentage to which batteries will be charged
following a low battery shutdown before powering connected
equipment.
Voltage Sensitivity
High sensitivity
High sensitivity
Medium sensitivity
Low sensitivity
The UPS detects and reacts to line voltage distortions by
transferring to battery operation to protect the connected
equipment.
In situations of poor power quality, the UPS may frequently
transfer to battery operation. If the connected equipment can
operate normally under such conditions, reduce the
sensitivity setting to conserve battery capacity and service
life.
Alarm Delay Control
Enable
• Enable
• Mute
• Disable
Mute ongoing alarms or disable all alarms permanently.
Shutdown Delay
90 seconds
• 0 s
• 90 s
• 180 s
• 270 s
• 360 s
• 450 s
• 540 s
• 630 s
Set the interval between the time when the UPS receives a
shutdown command and actual shutdown.