I. Module Description
The 1492-CM800-LD015 conversion module provides field wire signal conversion from a Modicon® B814-108 or
B840-108 , 8-pt relay output to a ControLogix 1756-OX8I , 8-pt relay output module. The conversion module
provides the mating connections to the B814-108 or B840-108 swing-arm (terminal block) with the attached field wires.
It routes those signals, via its 40-pin connector and a 1492-CABLEY pre-wired cable to compatible terminals of the
1756-OX8I. To maintain the fusing functionality of the B814-108 and B840-108 output modules the conversion module
provides a mechanical fuse for each of the 8 converted output points (refer to the Wiring Diagrams on pages 2 and 3).
II. Module Installation
The 1492-CM800-LD015 conversion module must be installed in a 1492 conversion base-plate and cover-plate assem-
bly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion
assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable
length is 003 (00.3 meters).
40-Pin Connector for 1492-CABLEY
Mating Connector for
B800 Terminal Block
Conversion Module
Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD0015
B814-108
1756-OX8I
1492-CABLE
Y
1492-CM800-LD0015
B840-108
1756-OX8I
1492-CABLE
Y
1492-CM800-LD015 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.
WARNING
Refer to conversion module Specifications Section: Maximum Operating Voltage