V. wiring diagrams (cont’d) – Rockwell Automation 1492-CM1771-LA002 Analog I/O Conversion Module User Manual
Page 5
(5)
V. Wiring Diagrams (Cont’d)
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
WARNING
Conversion: 1771-IFE to 1756-IF16 (Differential Voltage)
Conversion Module Installation and Application Considerations
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must
remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA002 module.
The pre-wired cable used between the 1492-CM1771-LA002 module and the 1756-IF16 [1492-CONACAB005C] provides a shield ground lug to
ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding
stud.
This design assumes that all inputs on the1771-IFE were connected to voltage transmitters. If there was a mix of current and voltage transmit-
ters, then modification of the pre-wired cable [1492-CONACAB005C] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16
Installation Manual for modification details.
The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range
is configured in the 1756-IF16.
Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring,
features and configuration details.
[Reference Doc: 41170-947 (Version 02)]
1771-WG Swing Arm
From 1771-IFE
Conversion Module
1492-CM1771-LA002
Cable
1492-CONACAB005C
1756-IF16
PN-114288
DIR 10000060099 (Version 01)
Publication 1492-IN046B-EN-E
1
6
7
8
9
5
10
15
20
19
21
11
12
13
14
16
17
18
2
3
4
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Orange/Black
Blue/Black
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
SH
Not Used
Channel 1+
Channel 1-
Channel 2+
Channel 2-
Channel 3+
Channel 3-
Channel 4+
Channel 4-
Not Used
Not Used
Module Common
Module Common
Channel 5+
Channel 5-
Channel 6+
Channel 6-
Channel 7+
Channel 7-
Channel 8+
Channel 8-
22
23
24
25
2
IN-0
IN-1
4
IN-2
6
IN-3
8
IN-4
12
IN-5
14
IN-6
16
IN-7
18
RTN
10
IN-9
22
IN-8
20
IN-11
26
IN-10
24
IN-15
36
IN-14
34
IN-13
32
IN-12
30
Transmitter
Power Supply
+
-