Rockwell Automation 900-TC8 Temperature / Process Controller User Manual
Installation operation menu, Temperature/ process controller
Installation
Operation menu
1618387-8C
Operation / Adjustment protection
The following table shows the relationship between settings and protect limits related to
Operation group and Adjustment group.
Protection function
Protection function is to prevent unwanted settings. It restricts the parameter to be used
or designates if operation of the key is valid or invalid.
Default setting : 0 (shaded)
Operation group
Adjustment group
Process value
Set point
Others
Group
Set value
0
○
◎
◎
◎
1
2
3
Parameter change protection
Parameter changes by key operation are restricted.
OFF “ ”: Parameter can be changed by key operation
ON “ ” : Parameter cannot be changed by key operation (“ ” will light.)
(Protect group parameters can all be changed.)
Initial setting/Communications protection
This protect level restricts movement to the initial setting group,
communications setting group and advanced function setting group.
Alarms
*1:
Upper and lower limits can be set for parameters 1, 4 and 5 to provide
for different types of alarm. These are indicated by the letter "L" and "H".
• Default = "2" (shaded)
Alarm type
1
0
2
3
4
5
6
7
8
9
10
11
12
Vary with "L", "H" values
Vary with "L", "H" values
Vary with "L", "H" values
No alarm function
Output off
Deviation upper/lower limit
standby sequence ON
Absolute value upper limit
Absolute value lower limit
Absolute value upper limit
standby sequence ON
Absolute value lower limit
standby sequence ON
LBA (only for alarm 1)
Deviation lower limit
standby sequence ON
Deviation upper limit
standby sequence ON
Deviation upper/lower range
Deviation upper limit
Deviation upper/lower limit
Deviation lower limit
Alarm output function
Positive alarm value (X)
L H
L H
L H
ON
OFF
SP
Negative alarm value (X)
X
ON
OFF
SP
ON
OFF
SP
X
X
ON
OFF
SP
ON
OFF
SP
ON
OFF
SP
X
X
X
ON
OFF
SP
ON
OFF
SP
ON
OFF
SP
X
X
X
X
ON
OFF
SP
ON
OFF
SP
ON
OFF
0
ON
OFF
X
X
0
ON
OFF
0
ON
OFF
X
X
0
ON
OFF
0
ON
OFF
X
0
ON
OFF
0
ON
OFF
X
0
Setting
* 1
* 1
* 1
Other functions
In addition to the aforementioned, there are alarm hysteresis, automatic return of
display mode and others in the advanced setting group.
Refer to "900-TC8 User's Manual" for details.
For communications details, please refer to "900-TC communications User's
Manual".
Specifications
Input type
*2: Error shown only for"Process value / Set point". Not shown for other status.
Error display (trouble shooting)
When an error has occurred, the No.1 display shows the error code. Take
necessary action according to the error code, referring the table below.
CN1
AT (auto-tuning)
“AT execute”
“ ” flashes
“AT cancel”
Also when AT execution ends, the display
automatically returns to “ ”.
No.1 display
Meaning
Internal circuit error
*2
A/D converter error
*2
Memory error
Input error
*2
(S. Err)
(E111)
(H. Err)
Check the wiring of inputs, disconnections, shorts
and input type.
Turn the power OFF then back ON again. If the display
remains the same, the controller must be repaired. If the
display is restored to normal, then a probable cause can
be external noise affecting the control system. Check for
After the correction of input error, turn the power OFF
then back ON again. If the display remains the same,
the controller must be repaired. If the display is restored
to normal, then a probable cause can be external noise
Action
OFF
Alarm
Control
output
Status at error
OFF
OFF
OFF
Operates
as above the
upper limit.
OFF
OFF
OFF
If the input value exceeds the display limit (–1999 to 9999), though it is within the control range, [[[[ will
be displayed under –1999 and above 9999. Under these conditions, control output and alarm
output will operate normally.
Refer to "900-TC User's Manual" for details of control range.
Set value
0
1
2
Initial setting
group
Communications
setting group
Advanced function
setting group
Default setting : 1
(shaded)
Temperature/ Process Controller
Model
900-TC8
Significance of CAUTIONS
41063-230-01 (2)
Printed In China
English
For detailed operating instructions, please refer to the 900-TC8 User's Manual
(900-UM007A-EN-E).
It can be found online at http://www.ab.com/manuals/.
Indicates information that, if not heeded, could result in injury,
damage to the product, or faulty operation.
ATTENTION
ATTENTION
Devices are Open Type, Listed Process Control Equipment and must be mounted in an enclosure.
More than one disconnect switch may be required to de-energize the equipment before servicing.
Signal inputs are SELV, limited energy.
Caution - To reduce risk of fire or Electrical shock, Do not interconnect the outputs of different Class 2
circuits.
Disconect power to device before installing or servicing.
Do not touch the terminals of controller when voltage is applied.
Do not allow metal fragments or lead wire scraps to fall inside this product. This may cause electric
shock, fire or malfunction.
Do not use this product where subject to flammable or explosive gas.
Never disassemble, repair or modify the product.
The life expectancy of the output relays varies greatly with the switching capacity and other switching
conditions. Always use the output relays within their rated load and electrical life expectancy. If an
output relay is used beyond its life expectancy, its contacts may become fused or burned.
Use copper wire only 24-14 AWG stranded or solid. Torque screws to 0.74 to 0.90 Nm or 6.5 to 8 lb-in.
Only two wires of same type and size per terminal. Correctly set the temperature controller settings to
match the control target. If the settings are not compatible with the control target, the product may
operate in an unexpected manner, resulting in damage to the product or an accident.
To maintain safety in the event of malfunction of the temperature controller, we recommend taking
safety measures, for example, installing an excessive temperature rise prevention alarm on a separate
line. If malfunction prevents control, they may result in an accident.
To reduce the risk of electrical shock or fire, install in a Pollution Degree 2 environment (controlled
environment relatively free of contaminants).
When the product is used under the circumstances or environment below, ensure adherence to
limitations of the ratings and functions. Also, take countermeasures for safety precautions such as
fail-safe installations.
*
Use under circumstances or environment which are not described in the
instruction manual.
*
Use for applications where death or serious property damage is possible and extensive
(1)
Do not use this product in the following:
* Places directly subject to heat radiated from heating equipment.
* Places subject to splashing liquid or oil atmosphere (exceeds NEMA 4X).
* Places subject to direct sunlight, could discolor or cause excessive heat.
* Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
* Places where intense temperature changes exceed the published ratings.
*
Places subject to icing and condensation.
* Places subject to vibration and large shocks.
(2)
Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3)
To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4)
Be sure to wire properly with correct polarity of terminals.
(5)
Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring.
(6)
Do not wire the terminals which are not used.
(7)
Allow as much space as possible between the controller and devices
that generate a powerful high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or
common wiring with the power lines when you are wiring to the terminals.
(8)
Use this product within the rated load and power supply.
(9)
Make sure that the rated voltage is attained within two seconds of turning the power
ON.
(10) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON
before you turn the controller ON.
(11) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator, and must be marked as
a disconnecting means for this unit.
(12) If you remove the controller from its case, or put the controller into its case, never touch nor
apply shock to the terminals and the electronic parts inside.
Make sure the electronic components and the case are not contacted when inserting the internal
mechanism. Always ensure power is OFF when doing any maintenance on the controller or
associated circuits.
(13) Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the
outside of the product.
(14)
Consider the 2 second delay required for the controller outputs to respond when you
design your control system.
(15)
If an option unit is used in the system refer to its Installation Manual before operating.
NOTICE
: Can be displayed and changed
: Can be displayed
: Can not be displayed and change
to other groups not possible
: Change to
other groups
possible
: Change to
other groups
not possible
• AT in Adjustment group
Designate " : AT execute" to execute
AT and " : AT cancel" to cancel AT.
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------------
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
Temperature input shift
(Unit: C or F)
Input shift upper limit
when 2 point input shift
is selected
Input shift lower limit
when 2 point input shift
is selected
Proportional band
Integral time
(Unit: secs)
Derivative time
(Unit: secs)
Dead band
Manual reset value
(Unit: %)
Hysteresis
(cool)
Soak time
SP ramp set value
MV upper limit
MV lower limit
Hysteresis
(heat)
AT execute =
on
AT cancel =
off
Cooling coefficient
Wait band
hys
1.0
chys
1.0
soak
1
sprt
off
ol-h
105.0
ol-l
-5.0
d
40
c-db
0.0
of-r
50.0
c-sc
1.00
wt-b
off
Heater Current 1
Value Monitor
(Unit: A) *7
Leakage Current 1
Value Monitor
(Unit: A) *7
Heater Burnout
Detection 1
(Unit: A) *7
HS Alarm 1
(Unit: A) *7
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
Setting range
Input type
Platinum
resistance
thermometer
Input
Thermocouple
Infrared
Thermosensor
Analog input
Use the following ranges for scaling: –1999 to 9999,
–199.9 to 999.9, Vary Depending on "L", "H" value
Temperature input type
Analog
input type
Setting
Setting range
Input type
Current input
Voltage input
Input
Use the following ranges for scaling: –1999
to 9999, –199.9 to 999.9, –19.99 to 99.99,
–1.999 to 9.999
4 - 20mA
0 - 20mA
1 - 5V
0 - 5V
0 - 10V
• The default is “0” (shaded).
Setting
0
1
2
3
4
• The default is “5” (shaded).
• will be display when a platinum resistance thermometer is mistakenly connected while input
type is not set for it. To clear the display, correct the wiring and cycle the power supply.
Operation group
Adjustment group
Protect group
Input type *3
Scaling upper limit
(only when setting analog input)
Scaling lower limit
(only when setting analog input)
Decimal point
(only when setting analog input)
°C/ °F selection
Set point upper limit
Set point lower limit
In ON/OFF control =
In 2-PID control =
Standard control =
Heating and cooling control =
(Select standard control or heating
and cooling control as required)
Control period (heat)
(Unit: Seconds)
Alarm 2 type: Specified models only
Alarm 3 type: Specified models only
Alarm 1 type: Specified models only
Control period (cool)
(Unit: Seconds)
°C=
°F=
(C stands for Celsius, F for Fahrenheit)
Self-tuning ON =
Self-tuning OFF =
In Reverse operation(heat) =
In Direct operation(cool) =
*3
*4
*3
*4
*3
*4
●Initial setting group
*
3: Refer to the adjoining tables for details of input types and alarm types.
*
4: Applicable only to models with alarm functions.
*
5: Operation is stopped when moved to the initial setting group.
(control/alarm are both stopped.)
*6: The grayed-out parameters may not be displayed according to the model and
parameter.
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
* 6
Transfer output type
Transfer output upper limit
Transfer output lower limit
Linear output type
* 6
* 6
* 6
* 6
Only the value set to the “ : temperature input shift” parameter is
applied to the entire temperature input range. When the process value is
200 °C, the process value is treated as 201.2 °C after input shift if the
input shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift if the input shift
Program pattern
POWER ON
Operation stopped.(control/alarm are both stopped.)
*5
The setting data for the 900-TC-8 is shown here as an
example.
sl-h
1300
sl-l
-200
cntl
onof
s-hc
stnd
st
on
* 6
Pt100
JPt100
K
J
T
E
L
U
N
R
S
B
10 - 70°C
60 - 120°C
115 - 165°C
140 - 260°C
0 - 50mV
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
(No. 1 display flushes
then the control stops)
Hold down
for at least
3 seconds
Hold down
for at least
1 second
Press
(less than 1 second)
Hold and keys
down for at least 1 second
Hold and keys
down for at least
3 seconds
–200 to 850 (°C)
–199.9 to 500.0 (°C)
0.0 to 100.0 (°C)
–199.9 to 500.0 (°C)
0.0 to 100.0 (°C)
–200 to 1300 (°C)
–20.0 to 500.0 (°C)
–100 to 850 (°C)
–20.0 to 400.0 (°C)
–200 to 400 (°C)
–199.9 to 400.0 (°C)
0 to 600 (°C)
–100 to 850 (°C)
–200 to 400 (°C)
–199.9 to 400.0 (°C)
–200 to 1300 (°C)
0 to 1700 (°C)
0 to 1700 (°C)
100 to 1800 (°C)
0 to 90 (°C)
0 to 120 (°C)
0 to 165 (°C)
0 to 260 (°C)
/ -300 to 1500 (°F)
/ -199.9 to 900.0 (°F)
/ 0.0 to 210.0 (°F)
/ -199.9 to 900.0 (°F)
/ 0.0 to 210.0 (°F)
/ -300 to 2300 (°F)
/ 0.0 to 900.0 (°F)
/ -100 to 1500 (°F)
/ 0.0 to 750.0 (°F)
/ -300 to 700 (°F)
/ -199.9 to 700.0 (°F)
/ 0 to 1100 (°F)
/ -100 to 1500 (°F)
/ -300 to 700 (°F)
/ -199.9 to 700.0 (°F)
/ -300 to 2300 (°F)
/ 0 to 3000 (°F)
/ 0 to 3000 (°F)
/ 300 to 3200 (°F)
/ 0 to 190 (°F)
/ 0 to 240 (°F)
/ 0 to 320 (°F)
/ 0 to 500 (°F)
• Up and Down keys
Use the keys to change the values displayed on
the No.2 display.
Each press of key increments or advances the
values displayed on the No.2 display.
Each press of key decrements or returns the
values displayed on the No.2 display.
• Group key
Use this key to change groups:
• Press the key and the key
together for at least 3 seconds to switch
to protect group .
Connections
(The applicability of the electric terminals varies with the type of machine.)
Mounting
Dimensions
Operation indicators
• ALM1: Alarm 1 indicator
Lit when alarm 1 is ON.
• ALM2: Alarm 2 indicator
Lit when alarm 2 is ON.
• ALM3: Alarm 3 indicator
Lit when alarm 3 is ON.
• HA: Heater burnout alarm/Heater Short alarm
indicator
Lit when a heater burnout or Heater Short
alarm has occurred.
• OUT1: Control output 1 indicator
Lit when control output 1 is ON and not lit
when it's OFF.
For a current output, lit except for a 0% output.
• OUT2: Control output 2 indicator
Lit when control output 2 is ON and
not lit when it's OFF.
• STOP: control stop indicator
Lights when event input or “Run/Stop”
is stopped during operation.
During control stop, functions other
than control output are valid.
• CMW: communications writing enable/
disable indicator
Lights when communications writing is
“enabled” and is out when it is
“disabled”.
• °C / °F : temperature unit
The temperature unit is displayed
when the configured display value is
a temperature.
When this parameter is set to “ °C”,
“C ” is displayed, and when set to
“ °F”, “F ” is displayed.
This flashes while ST(Self-Tuning) is
activated.
• : Protection indicator
Lit when Setting Change Protect is
ON (disables the Up and Down Keys).
• MANU: Manual output indicator
Lit when the Auto/Manual Mode is set
• Since the voltage output (control output 1) is not electrically insulated from the internal wiring, one or other of the control output
terminals must be left unearthed when using an earthed (grounded) type thermocouple thermometer. (Connection makes
measurements unreliable due to ground loop currents.) Basic insulation is provided between the voltage outputs (control output 2)
and internal circuits.
Dimensions (mm)
Names of parts on front panel
• No.1 display
Process value or set data symbol
• No.2 display
Set point, set data read-out value or changed
input value
• Mode key
Press this key to change the contents of
the display.
Press this button for 1 s or longer for
reverse scroll.
Adapter
Solderless terminal size: M3.5
In the pack:
• Main unit
• Watertight packing
• Adapter
• Instruction manual
• Terminal cover
* When drawing out from its case, press down the hook and turn a screwdriver to loosen the
screw on the lower part of the front panel.
15
14
13
12
19
18
17
16
11
10
9
8
7
6
2
1
5
4
3
Event Inputs
RS-485
Do not use
A (–)
B (+)
RS-232C
SG
RD
SD
•100-240V AC Type
•24V AC/DC Type
(no polarity)
Input power supply
Alarm 1. HBA/
HSA. input error
Alarm 2
Alarm 3
Alarm output
(relay output)
250V AC 3A
(resistive load)
•Relay output
250V AC 5A
(resistive load)
•Voltage output
12V DC 40mA
•Current output
DC4-20mA
DC0-20mA
load 600 max.
Control output 1
•Triac
relay output
250V AC 3A
(resistive load)
CTs: 900-CT1 or 900-CT3
(available separately)
•2 points
•1 point
Control output 2
CT1
CT2
CT1
–
mA
+
–
+
Analog input
V
CT input
PV
SV
ALM1
ALM2
ALM3
OUT1
STOP
OUT2
CMW
MANU
HA
PV
SV
ALM1
ALM2
ALM3
OUT1
STOP
OUT2
CMW
MANU
HA
•Voltage output:
12V DC 21 mA
TC/Pt multi-input
–
+
B
B
A
PV
SV
ALM1
ALM2
ALM3
OUT1
STOP
OUT2
CMW
MANU
HA
19
15
11
16
17
10
9
8
7
6
5
4
3
2
1
13
18
14
12
Watertight
packing
Terminal
cover
Individual mounting (mm)
Side-by-side mounting (mm)
• Insert the main unit through the mounting hole in the panel (1-8 mm
thickness). Insert the mounting brackets (supplied) into the fixing
slots located on the top and bottom of the rear case.
• Alternately tighten the top and bottom screws on the mounting fixtures
applying equal pressure a little at a time until the rachet rotates freely.
• When more than one machine is installed, make sure that the
ambient temperature does not exceed the specified limit.
Waterproofing is
impossible with
side-by-side installation.
When waterproofing is
required, fit watertight
packing on the backside
of front panel.
120 min
EV2
EV1
-
+
-
+
+0.8
0
92
+0.8
0
92
+0.6
0
45
+1
0
(48 x number of units-2.5)
Power supply voltage
100-240VAC type
24V AC/DC type
Operating frequency
50-60Hz
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Approx. 10VA (AC100-240V)
Approx. 5.5VA (AC24V)
Approx. 4W (DC24V)
Indication accuracy
Thermocouple, platinum resistance
(Ambient temperature: 23 C) thermometer:
(±0.5 % of indication value or ±1 C,
which is greater) ±1 digit max.
Analog
input:
±0.5 % FS ±1 digit max.
Event input
output current: approx. 7 mA per contact.
Contact input
ON:1 k max., OFF: 100 k min.
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Control output 1
Relay output: SPST-NO,
250 VAC, 5A(resistive load)
Voltage output: 12 VDC, 40 mA
Current output: 4 to 20 mA DC, and
0 to 20 mA load: 600 max.
Electrical life of relay:
100,000
operations
Control output 2
Voltage output: 12 VDC, 21 mA
Triac output: SPST-NO,
250 VAC, 3A(resistive load)
Electrical life of relay:
1 million operations (Long-life model)
Control method
ON/OFF or 2-PID control
Alarm output
Relay output: SPST-NO, 250 VAC,
3 A(resistive load),
electrical life: 100,000 operations
Ambient temperature
–10 to 55 C
(Avoid freezing or condensation)
Ambient humidity
RH 25 to 85%
Storage temperature
–25 to 65 C
(Avoid freezing or condensation)
Altitude Max.
2,000m
Recommended fuse
T2A, 250V AC, time-lag,
low-breaking
capacity
Weight
Approx. 260g (main unit only)
Degree of protection
Front panel: NEMA4X for indoor use (equivalent to IP66)
Rear case: IP20, Terminal section: IP00
Installation environment
Installation category II, pollution
degree 2 (as per IEC61010-1)
Memory protection
EEPROM (non-volatile memory)
(Number of write operations: 1,000,000)
Operation group should normally
be used during operations.
PV/SP
Set point during
SP ramp
Alarm value 1 *4
Alarm value upper limit 1
*4
Alarm value lower limit 1
*4
Alarm value 2 *4
Alarm value 3 *4
Alarm value upper limit 2
*4
Program start
Alarm value lower limit 2
*4
Heater Current 1
Value Monitor
(Unit: A) *7
Soak time remain
When control start =
When control stop =
Run/Stop
Alarm value upper limit 3
*4
Alarm value lower limit 3
*4
Operation / adjustment
protect
Initial / Communication
protect
Leakage Current 1
Value Monitor
(Unit: A) *7
91
112
96
84.5
11.5
48
44
78
2
Initial setting group enables users to specify their
preferred operating conditions (input type, alarm type,
control method, etc.)
Restricts which parameters can be
displayed or changed, and restricts
change by key operation.
Move to protect group
Adjustment group
Adjustment group is for entering set
values and shift values for control.
Parameter change protect