Conversion Module Installation and Application Considerations
The 1771-OW16 module output resistive current limits versus 1756-OW16I limits are as follows:
1771-OW16
1756-OW16I w/ 1492-CONCAB005Y
a) Current/Point
2A @ 250V AC
2A @ 240V AC
2A @ 30V DC
2A @ 30V DC
0.3A @ 150V DC
0.25A @ 125V AC
The 1492-CONCAB005Y is limited to 3A per pin.
The 1771-OW16 has N.O. and N.C. relay contact outputs. The 1756-OW16I has N.O. relay contact outputs only. The conver-
sion module does not convert the N.C. to N.O. contacts. If the 1771-OW16 N.C. outputs were being used, the installer must
rewire the 1771-WN swing arm and move the N.C. wires to the N.O. output terminals. In addition, the control Logix programming
will need to be changed to simulate a N.C. relay with this output.
Refer to your 1771-OW16 and 1756-OW16I Installation Manual wiring schematics and diagrams for more details.
Ensure 1756 output module ratings are not exceeded.
Reference Doc: 41170-940 (Version 01)]
V. Wiring Diagrams
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and input module). Read and understand these
considerations before installation.
WARNING
Conversion: 1771-OW16 to 1756-OW16I
1
2
17
20
23
26
4
3
6
5
8
7
10
9
12
11
14
13
16
15
19
18
22
21
25
24
28
27
31
30
34
33
37
36
40
39
29
32
35
38
Output 14 (NO)
Output 16 (NO)
Output 15 (NO)
Output 04
Output 06
Output 05
Output 07
Output 00
Output 02
Output 01
Output 03
Output 10 (NO)
Output 12 (NO)
Output 11(NO)
Output 13 (NO)
Output 17 (NO)
Output 14 (NC)
Output 15 (NC)
Output 16 (NC)
Output 17 (NC)
1
2
3
4
5
6
7
8
9
10
11
12
13
15
16
17
18
19
20
14
21
22
23
24
25
26
27
28
29
30
31
32
33
35
36
37
34
OUT-0 N.O.
2
1
OUT-1 N.O.
4
3
OUT-2 N.O.
6
5
OUT-3 N.O.
8
7
OUT-4 N.O.
10
9
OUT-5 N.O.
12
11
OUT-6 N.O.
14
13
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
OUT-7 N.O.
16
15
OUT-8 N.O.
18
17
OUT-9 N.O.
20
19
OUT-10 N.O.
22
21
OUT-11 N.O.
24
23
OUT-12 N.O.
26
25
OUT-13 N.O.
28
27
OUT-14 N.O.
30
29
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
OUT-15 N.O.
32
31
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L1-8
L1-9
L1-10
L1-11
L1-12
L1-13
L1-14
L1-15
L1
L2
Common 00
Common 01
Common 02
Common 03
Common 04
Common 05
Common 06
Common 07
Common 10
Common 11
Common 12
Common 13
Common 14
Common 15
Common 16
Common 17
Output 10 (NC)
Output 11 (NC)
Output 12 (NC)
Output 13 (NC)
+
-
LOAD
LOAD
PN-114283
DIR 10000060094 (Version 01)
Publication 1492-IN041B-EN-E
Printed in U.S.A.
Conversion Module
1492-CM1771-LD011
Cable
1492-CONCAB005Y
1756-OW16I
1771-WN Swing Arm
From 1771-OW16