Steps 3 and 4 step 2, 180a dc bus fuse, Diode replacement – Rockwell Automation 1336R REGEN 78A, 180A DC Bus Fuse Repl. User Manual
Page 3

1336 REGEN 78A and 180A Converter DC Bus Fuse
&
Diode Replacement
3
1336 REGEN-5.15 May, 1998
DANGER
DANGER
S
TORQUE TERM. TO 6 N-m (52 lb-in)
T
USE 75
°
C COPPER WIRE ONLY
R
DC-
DC+
TE
PE
PE
120
RT
N
120
VA
C
CAT 1336R-VB180CNV-AN-HAP
SER A
118.7-143.7
AC INPUT
K W
VOLTS
A
PH
HZ
AC OUTPUT
DC OUTPUT
REFER TO USER MANUAL FOR
INSTALLATION INSTRUCTIONS
180.4
–
–
–
–
33
–
–
195.6
380-480
118.7-143.7
3
50/60
380-480
ALLEN-BRADLEY
MADE IN U.S.A.
UL
®
LIST
ED 966X
IN D
C O N T E
Q
UL
®
LIST
ED 966X
IN D
C O N T E
Q
C
®
t o p p e d
S
. 0 0 H z
0
+
! DANGER
RISK OF SHOCK
REPLACE AFTER
SERVICING
!
DANGER
ELECTRICAL SHOCK HAZARD FROM
ENERGY STORAGE CAPACITORS
VERIFY LOW VOLTAGE DISCHARGE
BEFORE SERVICING.
SEE INSTRUCTION MANUAL.
! DANGER
RISK OF SHOCK
REPLACE AFTER
SERVICING
Clear Plastic
Shield
Bus Fuse
Fastened to Bus Bar with
Two Bolts and Washers
Upper Bus Bar
Lower
Bus Bar
Diode Module
Fastened to Bus Bar
with Two Screws
and Washers
Steps 3 and 4
Step 2
1.
Remove and lock-out all incoming
power to the 1336 REGEN Line
Regeneration Package.
a.
Remove the Precharge Unit front
cover. Measure the voltage at input
power terminals R1–S1–T1 and
terminal block TB1 with a
voltmeter to ensure that no voltage
is present.
b.
Remove the Converter front cover.
Measure the voltage at input power
terminals R2–S2–T2 with a
voltmeter to ensure that no voltage
is present.
2.
Remove the clear plastic shield.
3.
Remove the open DC bus fuse and
diode module even if the module
appears good. Removing the diode
module assures that undetected
damage will not cause a malfunction
at a later date.
4.
Install the new DC bus fuse and
diode module included with the kit.
Torque the fuse bolts to 11.0-12.5
N-m (97-111 lb.-in.). Torque the
diode module screws to 4 N-m (35.4
lb.-in.).
5.
Reinstall the protective shield and
Converter cover.
180A DC Bus Fuse
&
Diode Replacement
!
ATTENTION:
Replace any guards or shields
previously removed before reapplying power to the
Converter or 1336 REGEN Line Regeneration
Package. Failure to replace guards or shields may